System Set-Up
Hydro Kit
Installation Manual
63
ENGLISH
Function text inside
remote
Range
Short explanation
Mid Temp.
High Temp.
DHW time setting
- Operation Holding Time 5 min ~
95 min (30 min Default)
- Stop Holding Time 0 min ~
600 min (180 min default)
- Operation Holding Time 5 min ~
95 min (30 min Default)
- Stop Holding Time 0 min ~
600 min (30 min default)
Set the hot water maintenance /
suppression time.
Pump frequency setting
(LPM)
- 15 LPM ~ 92 LPM
(46 LPM Default)
N/A
Setting for water flow rate in water piping.
TH on/off Variable,
heating air
- Type : 0, 1, 2, 3 (Default 0)
The temperature of the heating air can be
adjusted according to the field
environment preparing for heating claims.
TH on/off Variable,
heating water
- Type : 0, 1, 2, 3 (Default 0)
The temperature of the heating water can
be adjusted according to the field
environment preparing for heating claims.
TH on/off Variable,
cooling air
- Type : 0, 1, 2, 3 (Default 0)
N/A
The temperature of the cooling air can be
adjusted according to the field
environment preparing for cooling claims.
TH on/off Variable,
cooling water
- Type : 0, 1, 2, 3 (Default 0)
N/A
The temperature of the cooling water can
be adjusted according to the field
environment preparing for cooling claims.
TH on/off Variable, DHW - Type : 0, 1, 2, 3 (Default 0)
It is a function to set the step value to
adjust the hot water temperature thermal
on / off according to the field environment.
Heating temp. setting
- 00 : Leaving (Default)
- 01 : Entering
It is a function to set the water pipe
temperature control standard for heating
in accordance with the field environment.
Cooling temp. setting
- 00 : Leaving (Default)
- 01 : Entering
N/A
It is a function to set the water pipe
temperature control standard for cooling
in accordance with the field environment.
Pump setting in heating
- Type : Time, Always (Time default)
- OFF Time : 1 min ~ 60 min (1 min default)
- ON Time : 1 min ~ 60 min (2 min default)
It is a function to set water pump
operation / delay time option for heating.
Pump setting in cooling
- Type : Time, Always
(Always default)
- OFF Time : 1 min ~ 60 min
(1min default)
- ON Time : 1 min ~ 60 min
(2 min default)
N/A
It is a function to set water pump
operation / delay time option for cooling.
Forced operation
- Value 1 : ON , OFF(On Default)
- Value 2 Forced Period : 20 ~ 180 hr (20 hr Default)
- Value 3 Pump Operating Time : 1 ~ 10 min (10 min Default)
It is a function to deactivate the logic that
drives the water pump itself.
CN_CC
- D/C (Dry Contact) Automatic (Default)
- D/C (Dry Contact) Not installed
- D/C (Dry Contact) installed
Function should be set correct depending
on optional dry-contact.
Smart Grid (SG)
- Not Use (Default)
- Use
- Step 0, Step 1 , Step 2 (Mode Selection)
The function to enable / disable the SG
Ready function and to set the reference
value at the step 2.