Installation
Hydro Kit
Installation Manual
21
ENGLISH
3) Water Tank(DHW) + Floor Heating Installation(Default)
- For DHW / Floor Heating operation , ‘Dip switch #2’ should be set correctly.
- For sensing air temperature at specific area, remote temperature sensor(PQRSTA0) or wired
remote controller could be choose, depending on the ‘Dip switch #3’ setting.
*please refer the “System Set-Up, Dip Switch Setting”
- Wi-Fi module(PWFMDD200/105 cm) connected to ‘CN-WF’ on Hydro kit PCB. To increase the
length between Wi-Fi modem and Hydro Kit, please purchase USB Extension Cable(PWYREW000,
10 m)
- In case of floor cooling, please make sure to set cooling cut off temperature for preventing
condensation on the floor
- For 3-way, 2-way valve control, please refer the “Accessories Installation”
- The Heating operation mode of the hot water tank is not a mode selection by the remote controller,
it changes the 3-way valve direction to Water Tank base on the water tank temperature.
- It is impossible to operate Hot water(DHW) during cooling mode.
13
12
1
1
3
3
11
10
9
8
6
5
4
2
7
Drainage
1
Water Supply
FCU
14
(Cooling → Close)
PQRSTA0
Wired Remote
Controller
Wi-fi Module
(PWFMDD200)
1
Water Supply
Field Supply
LG Supply
1
Shut-Off valve
8
Balancing valve with flow meter
2
Expansion tank
9
Automatic air separator
3
Service port(Drain valve)
10
Pressure safety relief valve
4
Magnetic filter(Recommended)
11
Pressure meter
5
Water Pump
12
Check valve
6
Strainer
13
DHW
1)
(Sanitary Water) Tank
7
Flow switch (Included in product)
14
Water Tank temperature Sensor (12 m)
Mode
Condition
3-way valve direction
2-way valve
Cooling
FCU – ‘Not use’
Under Floor
Open
FCU – ‘Use’
Under Floor
Close
Heating
Priority – ‘DHW’
DHW / Sanitary Water Tank
No control
Priority – ‘UFH’
Under Floor
No control
NOTICE