18 Room Air Conditioner
Installation
• Tighten the flare nut with a wrench.
• When extending the drain hose at the indoor unit,
install the drain pipe.
5. Wrap the insulation material around the con-
necting portion.
• Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
• Wrap the area which accommodates the rear pip-
ing housing section with vinyl tape.
• Bundle the piping and drain hose together by
wrapping them with vinyl tape for enough to cover
where they fit into the rear piping housing section.
For left rear piping
1. Route the indoor tubing and the drain hose to
the required piping hole position.
2. Insert the piping, drain hose, and the connecting
cable into the piping hole.
mm
inch
kg.m
Ø6.35
1/4
1.8
Ø9.52
3.8
4.2
Ø12.7
1/2
5.5
Ø15.88
5/8
6.6
Ø19.05
3/4
6.6
Outside diameter
Torque
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection
pipe
Connecting cable
Vinyl tape
(wide)
Wrap with vinyl tape
Indoor
unit pipe
Pipe
Drain hose
Connecting
cable
Drain pipe
Connecting cable
Содержание AS-W096QGG1
Страница 48: ...48 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Страница 49: ...Service Manual 49 Schematic Diagram Outdoor AS W096_Series AS W126_Series ...
Страница 50: ...50 Room Air Conditioner Schematic Diagram Outdoor AS W186_Series AS W246_Series ...
Страница 55: ...Service Manual 55 Schematic Diagram OUTDOOR MAIN P W B ASSEMBLY AS W096QGG1 AS W126RGH1 BOTTOM VIEW TOP VIEW ...
Страница 84: ...P No 3828A20195S February 2007 Printed in Korea ...