Service Manual 33
Operation
Cooling mode operation
• Operating frequency of compressor depend on the difference of the temperature.
(= intake air Temp.- Compressor off Temp.
• Compressor off temp.= setting temp. -0.5°C
on temp. = setting temp. +0.5°C
• If compressor operates at some operating frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature stay at the temperature between setting temp. -0.5°C and setting temp.
-1.0°C for 3 minutes continuously.
- When intake air temperature reaches below the temperature of setting temp. -1.0°C.
• Compressor 2 minutes delay
- The compressor can restart minimum 2 minutes later after compressor off.
Temp. differences
Comp. Operating frequency
over 3.0°C
Step 7
over 2.5°C
Step 6
2.0~2.49°C
Step 5
1.5~1.99°C
Step 4
1.0~1.49°C
Step 3
0.5~0.99°C
Step 2
0.0~0.49°C
Step 1
[The operating freq. step of comp.]
[The targeting operating freq. of comp. each model]
Model
AS-W096QGG1
35
40
47
57
62
65
69
AS-W126RGH1
35
40
53
60
70
75
80
AS-W186TGH1
20
32
58
64
72
80
90
AS-W246TGH1/TLG1
35
48
53
57
61
64
67
Comp. Operating frequency
Step 1
Step 2
Step 3
Step 4
Step 5(Fc)
Step 6
Step 7
Содержание AS-W096QGG1
Страница 48: ...48 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Страница 49: ...Service Manual 49 Schematic Diagram Outdoor AS W096_Series AS W126_Series ...
Страница 50: ...50 Room Air Conditioner Schematic Diagram Outdoor AS W186_Series AS W246_Series ...
Страница 55: ...Service Manual 55 Schematic Diagram OUTDOOR MAIN P W B ASSEMBLY AS W096QGG1 AS W126RGH1 BOTTOM VIEW TOP VIEW ...
Страница 84: ...P No 3828A20195S February 2007 Printed in Korea ...