32 Room Air Conditioner
Operation
• If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in
cooling cycle operation mode,
➔
compressor, outdoor fan are turned off.
• When indoor pipe temp. is 7°C or higher after 2 min pause of compressor
➔
compressor, outdoor fan is turned on according to the condition of the room temperature.
• Control condition : The system operates standard operation without this condition as follows.
Setting temperature <25°C
Indoor fan speed
≤
low speed
Outdoor temperature < 30°C
• Control method
In operation for 5~20 minutes in
,
,
conditions, return to the previous COMP STEP after operation for
5~40 minutes at the COMP STEP 3.
Comp. free
Comp. Step 4
Comp. Step 2
Comp. off
0˚C
3˚C
6˚C
7˚C
Indoor pipe
temp.
Protection of the evaporator pipe from frosting
Protection of the indoor fan from droplet formation (Enclosure sweat and condensed disposal test)