34 Room Air Conditioner
Operation
Healthy Dehumidification mode operation
• When the dehumidification operation is set by the remote controller the intake air temperature is detected and
the setting temp. is automatically set according to the intake air temperature.
• When intake air temp reaches above the temp of s1.0°C, condition of compressor same as cooling
mode operation.
• When intake air temperature reaches bolow the temp of setting –1.0°C, compressor operate step1~step3 and
indoor fan speed repeatly operate low or stop.
Intake air Temp.
32°C
≤
intake air temp.
26°C
≤
intake air temp. < 32°C
24°C
≤
intake air temp.< 26°C
18°C < intake air temp. < 24°C
intake air temp.
≤
18°C
Setting Temp.
25°C
25°C
intake air temp. -1°C
intake air temp. -0.5°C
18°C
Содержание AS-W096QGG1
Страница 48: ...48 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Страница 49: ...Service Manual 49 Schematic Diagram Outdoor AS W096_Series AS W126_Series ...
Страница 50: ...50 Room Air Conditioner Schematic Diagram Outdoor AS W186_Series AS W246_Series ...
Страница 55: ...Service Manual 55 Schematic Diagram OUTDOOR MAIN P W B ASSEMBLY AS W096QGG1 AS W126RGH1 BOTTOM VIEW TOP VIEW ...
Страница 84: ...P No 3828A20195S February 2007 Printed in Korea ...