Troubleshooting Guide
- 80 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Location of 4way valve connector on
Main PCB (marked as 4way, CN09)
** Confirm the 4way valve coil is inserted to the end
* Measure the resistance of 4way valve
**** Check the output voltage of terminal socket
during heating operation
*** When power is supplied in order as follow
ODU information is displayed one after the other at main PCB 7-segment
1. Model ID
→
5HP : 60, 6HP : 61, 8HP : 62, 10HP : 63, 12HP : 64, 14HP : 65
2. Total Capacity
→
Displayed with HP
3. ODU Type
→
HEAT PUMP : 2, Cooling : 0
4. Normal mode : 25
5. Refrigerant
→
R410a : 41
***** Checking method for outside unit of 3unit system
➀
Close all the SVC valves of high / low pressure common pipe
➁
Operate system
➂
Check the difference of high and low pressure with LGMV for each unit
➃
If there is a unit in which the difference is not increased then the 4way valve of that unit is defective