Self-diagnosis function
3. Self-diagnosis function
Error Indicator
• This function indicates type of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outside unit
control board as shown in the table.
• If more than two troubles occur simultaneously, low number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error display method
1st and 2nd LED of 7-segment refers to the error number and the 3rd LED refers to the outside unit number.
Ex) 011: Error No. 1 of outside unit No. 1
011
➠
051: Error No. 105 of outside unit No. 1
Display
Error item
Root cause of error
Indoor unit
0
1
-
Indoor unit air temperature sensor error
Indoor unit air temperature sensor disconnection or short
circuit
0
2
-
Inlet pipe temperature sensor of indoor
unit
Indoor unit pipe inlet temperature sensor disconnection or
short circuit
0
3
-
Communication error between wired
remote controller and indoor unit
Occurs when indoor unit communication signal is not
received from the wired remote controller
0
4
-
Indoor unit drain error
Drain pump and float switch error
0
5
-
Communication error between outside unit
and indoor unit
When the indoor unit does not receive the outside commu-
nication signal continuously for 5 minutes or more
0
6
-
Indoor unit pipe outlet temperature sensor
error
Indoor unit pipe outlet temperature sensor disconnection
or short circuit
0
9
-
Indoor unit EEPROM error
Communication error between MICOM and EEPROM or
when there is
no indoor unit EEPROM data
1
0
-
Indoor unit BLDC motor feedback signal
error
When motor connector is removed or defective
1
7
-
Inlet Air temperature sensor of FAU
Air temperature sensor of indoor unit is open or short
Outside unit
2
1
1
Outside unit inverter compressor IPM fault
Outside unit inverter compressor drive IPM error
2
2
1
Inverter Board Input Over Current (RMS)
of Outside Unit
Outside Unit Inverter Board Input Current excess (RMS)
2
3
1
Outside unit inverter compressor DC link
under-voltage
DC voltage is not charged after outside unit operating
relay is turned on
2
4
1
Outside unit high pressure switch
Compressor maintenance by outside unit high pressure
switch Flow rate insufficiency or flow switch trouble of out-
side unit