Function
3.1.2 Pressure control on heating mode
■
High pressure control
■
Low pressure control
❈
Frequency holding : frequency (or RPM) is not increasing (can decrease)
3.1 Pressure protection control
3.1.1 Pressure control on cooling mode
■
High pressure control
■
Low pressure control
❈
Frequency holding : frequency (or RPM) is not increasing (can decrease)
3. Protection control
Pressure Range
Compressor
Hot_gas
Pd ≥ 4003kPa
Stop
On
Pd > 3676kPa
-5Hz/4sec.
Pd ≥ 3448kPa
Normal control
Pd < Target press
Normal control
Off
Pressure Range
Compressor
Hot_gas
①
Ps ≤ 739kPa
after 3sec.
-5Hz/7sec.
-
②
Ps > 739kPa
Normal control
Pressure Range
Compressor
Hot_gas
①
Ps ≤ 229kPa
after 10sec.
Stop
On
②
Ps ≤ 229kPa
before 10sec.
-5Hz/7sec.
③
Ps ≤ 242kPa
Normal control
Ps ≥ 399kPa
Normal control
Off
Pressure Range
Compressor
Hot_gas
Pd ≥ 4003kPa
Stop
On
Pd > 3676kPa
-5Hz/4sec.
Off
Pd ≥ 3448kPa
Frequency holding
Pd < 3448kPa
Normal control