Function
3.5 Pressure switch
- The state of pressure sensing switch is normally on. It has small electric current from 220V AC. Never touch
the connecting terminal with hand nor short two wires directly.
3.4 Liquid back control
■
Cooling mode
■
Heating mode
❇
The logic starts after 9min. on heating mode and 4min. on cooling mode from the compressor running.
Tdis < Tc + 12˚C
Discharge temperature
Indoor unit ’s EEV
Normal SH control
Tdis > Tc + 16 ˚C
SH increasing control
SH increasing control
Tdis < Tc + 17˚C
Discharge temperature
Outside unit ’s EEV
Normal SH control
Tdis > Tc + 18 ˚C
Содержание ARWN038GA2