Troubleshooting Guide
- 69 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
■
Error diagnosis and countermeasure flow chart
1. Bad connection of air temperature connector
2. Defect of air temperature connector (Open/Short)
3. Defect of outside PCB
1. Bad connection of air temperature connector
2. Defect of air temperature connector (Open/Short)
3. Defect of outside PCB
1. Bad connection of air temperature connector
2. Defect of air temperature connector (Open/Short)
3. Defect of outside PCB
Error No.
Error Type
Error Point
Main Reasons
Abnormal value of
sensor (Open/Short)
Abnormal value of
sensor
(Open/Short)
Abnormal value of
sensor (Open/Short)
Sensor error of
outside air temper-
ature
Piping temperature
sensor error of heat
exchanger in
outside unit heat
exchanger (A,B)
Compressor suc-
tion temperature
sensor error
44*
46*
45*
Is sensor connected
to PCB correctly??
Is sensor value correct?*
Connect sensor to PCB correctly
Replace sensor
Replace corresponding
outside unit PCB
Yes
No
No
Yes
* If value is 100k
≠
(open) or 100
Ø
(short), error occurs
NB: Resistance value of temperature sensor change according to
temperature
It is normal if value shown as below (5% error)
Sensor of air temperature: 10C = 20.7k : 25C= 10k : 50C= 3.4k
Sensor of piping temperature: 10C = 10k : 25C= 5k : 50C= 1.8k