1. Basic control
Function
1.2 Compressor control
Fuzzy control : Maintain evaporating temperature(Te) to be constant on cooling mode and condensing tem-
perature(Tc) on heating mode by Fuzzy control to ensure the stable system performance.
(Tc:47 ~ 51°C (117 ~ 124°F), Te:2 ~ 5°C (36 ~41°F))
(1) Cooling mode
Te can be set by initial DIP switch setting. (Standard, Long pipe)
(2) Heating mode
Tc can be set by initial DIP switch setting. (Standard, Long pipe)
Note:
By setting DIP switch, Te and Tc are decided simultaneously.
1.1 Normal operation
Compressor
Main EEV
4 way valve
Fuzzy control
Full open
OFF
OFF
Fuzzy control
Fuzzy control
ON
Cooling operation
Heating operation
Actuator
Stop
Close
Stop state
Fuzzy Control
Stop
Set frequency
Fuzzy control start
Target
Inverter linear control as cooling and heating load increasing
System Capacity
Cooling and heating load
(Linear Control)
(Linear Control)
(Linear Control)
Inverter
Inverter
Compressor
Compressor
Inverter
Compressor