8. Installation
29
MULTI/SINGLE
Indoor unit
Ceiling Suspended Unit
8.4 Connecting Cables between Indoor Unit and Outdoor Unit
8.4.1 General instructions
• All field supplied parts and materials, electric works must conform to local codes. Use copper wire only.
• Follow the
"WIRING DIAGRAM”
attached to the unit body to wire the outdoor unit, indoor units and the remote
controller.
• All wiring must be performed by an authorized electrician.
• A circuit breaker capable of shutting down the power supply to the entire system must be installed.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
– Never fail to have separate power specially for the air conditioner.
– Provide a circuit breaker switch between power source and the unit.
– Confirm the Specification of power source.
– Confirm that electrical capacity is sufficient.
– Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
– Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
– Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
– The following troubles would be caused by voltage drop-down.
» Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
» Proper starting power is not given to the compressor.
8.4.2 Wiring connection
• Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
respectively.
• In case of the system with multiple indoor units, mark each indoor unit as unit A, unit B, etc and be sure the
terminal board wiring to the outdoor unit and indoor units are properly matched. If wiring and piping between the
outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.
8.4.3 Clamping of cables
1. Arrange 2 power cables on the control panel.
2. First, fasten the steel clamp with a screw to the inner boss of control panel.
3. For connecting of communication (transmission) cable, put the cable(or thinner cable) on the clamp and tighten
it with a plastic clamp to the other boss of the control panel. In case that communication (transmission) cable is
not needed to connect, fix the other side of the clamp with a screw strongly.
Содержание AMNW07GSJL0
Страница 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 08B Replaces 0CTI5 08A P No MFL67502513 ...
Страница 2: ...MULTI SINGLE Indoor unit General information Product data ...
Страница 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...
Страница 34: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 1 5 Wiring Diagrams Deluxe AMNW07GSJL0 DM07RP NSJ ...
Страница 142: ...7 MULTI SINGLE Indoor unit Wall Mounted Unit 4 5 Wiring Diagrams ZJNW30GRLA1 US30F NR0 ZJNW36GRLA1 US36F NR0 ...
Страница 203: ...5 MULTI SINGLE CAC Indoor unit ART COOL 3 Dimensions ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...
Страница 205: ...7 MULTI SINGLE CAC Indoor unit ART COOL 5 Wiring Diagrams Models ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...