4
MULTI/SINGLE
Indoor unit
ART COOL Silver
2. Specifications
Model Name
S3NM09JASZA
[AC09SQ NSJ]
Power Supply
V, Ø, Hz
220-240, 1, 50
220, 1, 60
Capacity
Cooling
kW
2.5
Heating
kW
3.3
Power Input
Min./Nom./Max.
W
11 / 18 / 30
Running Current
Min./Nom./Max.
A
0.10 / 0.16 / 0.20
Exterior Color code
-
Munsell N8.5 (RAL 9018)
Dimensions
Body
W x H x D
mm
837 × 308 × 192
W x H x D
inch
32-15/16 × 12-1/8 × 7-9/16
Shipping
W x H x D
mm
909 × 383 × 256
W x H x D
inch
35-25/32 × 15-3/32 × 10-3/32
Weight
Body
kg (lbs)
9.9 (21.8)
Shipping
kg (lbs)
13.6 (30.0)
Heat Exchanger
(Row x Column x Fins per inch) x
No.
-
(2 × 15 × 21) × 1
Face Area
m
2
(ft
2
)
0.19 (2.05)
Corrosion Protection
-
PCM
Fin Type
-
Slit
Material, Tube / Fin
-
Cu / Al
Fan
Type
-
Cross Flow Fan
Air Flow Rate
(Cooling)
SH / H / M / L
m
3
/min
12.5 / 10.0 / 7.5 / 4.2
ft
3
/min
441 / 353 / 265 / 148
(Heating)
SH / H / M / L
m
3
/min
13.0 / 10.0 / 7.2 / 5.6
ft
3
/min
459 / 353 / 254 / 198
Fan Motor
Type
-
BLDC
Output
W x No.
30 x 1
Sound Pressure Level
(Cooling)
SH / H / M / L / SL
dB(A)
45 / 41 / 35 / 27 / 19
(Heating)
SH / H / M / L / SL
dB(A)
45 / 41 / 35 / 27 / -
Sound Power Level
Rated
dB(A)
59
Piping Connections
Liquid
mm(inch)
Ø 6.35 (1/4)
Gas
mm(inch)
Ø 9.52 (3/8)
Drain
O.D. / I.D.
mm
21.5 / 16.0
Safety Devices
-
Fuse
-
Thermal Preotector for Fan Motor
Connections Method
-
Flared
Power and Communication Cable (included Earth)
No. x mm
2
(AWG)
4C x 1.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions
and values are normally higher in actual operation(Sound Pressure : LG Internal standard, Sound Power : EN 12102 (ISO 3741).
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
Содержание AMNW07GSJL0
Страница 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 08B Replaces 0CTI5 08A P No MFL67502513 ...
Страница 2: ...MULTI SINGLE Indoor unit General information Product data ...
Страница 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...
Страница 34: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 1 5 Wiring Diagrams Deluxe AMNW07GSJL0 DM07RP NSJ ...
Страница 142: ...7 MULTI SINGLE Indoor unit Wall Mounted Unit 4 5 Wiring Diagrams ZJNW30GRLA1 US30F NR0 ZJNW36GRLA1 US36F NR0 ...
Страница 203: ...5 MULTI SINGLE CAC Indoor unit ART COOL 3 Dimensions ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...
Страница 205: ...7 MULTI SINGLE CAC Indoor unit ART COOL 5 Wiring Diagrams Models ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...