21
MULTI/SINGLE
Indoor unit
Ceiling Suspended Unit
8. Installation
8.1 Selection of the best location
• The place where room air circulation is good.
• Do not install the unit near the door.
• There should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
• The place where the indoor unit can be connected with outdoor unit easily.
• The place where the unit is leveled.
• The place shall allow easy water drainage.
• The place where bear a load exceeding four times of the indoor unit weight.
• The mounting ceiling or wall should be solid enough to protect it from the vibration.
• The place where the unit is not affected by an electrical noise.
• The place where noise prevention is taken into consideration.
• The place where the maintenance space for product is sufficient. (The servicing inspection hole of the ceiling
should be larger than the indoor unit.)
• The selection of the servicing inspection hole should be approved by the customer.
• There should not be any heat source or steam near the unit. Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
• Please read the instruction sheets completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards.
• Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning,
temperature control, etc.)
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
Air conditioner or
Ducted air diffuser
Take enough
distance
※
According to type of indoor unit, external appearance
or installed structure could be different.
(Min. 500 mm)
Содержание AMNW07GSJL0
Страница 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 08B Replaces 0CTI5 08A P No MFL67502513 ...
Страница 2: ...MULTI SINGLE Indoor unit General information Product data ...
Страница 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...
Страница 34: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 1 5 Wiring Diagrams Deluxe AMNW07GSJL0 DM07RP NSJ ...
Страница 142: ...7 MULTI SINGLE Indoor unit Wall Mounted Unit 4 5 Wiring Diagrams ZJNW30GRLA1 US30F NR0 ZJNW36GRLA1 US36F NR0 ...
Страница 203: ...5 MULTI SINGLE CAC Indoor unit ART COOL 3 Dimensions ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...
Страница 205: ...7 MULTI SINGLE CAC Indoor unit ART COOL 5 Wiring Diagrams Models ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...