6. External Static Pressure & Air Flow
24
Ceiling Concealed Duct - Middle Static Pressure
ZBNW48GM3A1 [UM48F N30], ZBNW60GM3A1 [UM60F N30]
Note
The above table shows the correlation between the air rates and E.S.P.
Setting value
Static Pressure (mmAq(Pa))
4(39)
5(49)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
Air Flow Rate [m³/min]
70
27.4
25.1
-
-
-
-
-
-
75
31.6
29.5
26.1
-
-
-
-
-
80
36.3
34.0
30.8
25.9
-
-
-
-
85
40.6
38.4
35.4
30.6
23.2
-
-
-
90
45.4
42.9
40.1
35.2
28.1
21.0
-
-
95
49.7
47.3
44.8
39.9
33.1
26.3
19.5
-
100
56.1
51.8
49.4
44.6
38.0
31.7
25.2
22.6
105
-
56.2
54.1
49.2
43.0
37.1
31.0
28.5
110
-
-
58.8
53.9
47.9
42.4
36.7
34.4
115
-
-
-
58.6
52.9
47.8
42.5
40.3
120
-
-
-
-
57.8
53.1
48.2
46.1
121
-
-
-
-
-
54.2
49.4
47.3
Содержание AMNW07GSJL0
Страница 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 08B Replaces 0CTI5 08A P No MFL67502513 ...
Страница 2: ...MULTI SINGLE Indoor unit General information Product data ...
Страница 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...
Страница 34: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 1 5 Wiring Diagrams Deluxe AMNW07GSJL0 DM07RP NSJ ...
Страница 142: ...7 MULTI SINGLE Indoor unit Wall Mounted Unit 4 5 Wiring Diagrams ZJNW30GRLA1 US30F NR0 ZJNW36GRLA1 US36F NR0 ...
Страница 203: ...5 MULTI SINGLE CAC Indoor unit ART COOL 3 Dimensions ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...
Страница 205: ...7 MULTI SINGLE CAC Indoor unit ART COOL 5 Wiring Diagrams Models ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...