8. Installation
27
MULTI/SINGLE
Indoor unit
Ceiling Suspended Unit
8.3 Indoor Unit Drain Piping
8.3.1 Drain piping of indoor unit
• Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent
reversal flow.
• During drain piping connection, be careful not to exert force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor unit and drain piping fittings should be referenced
from ‘Specifications’ of each models.
– Piping material: Use the Polyvinyl chloride pipe.
• Be sure to install heat insulation on the drain piping.
– Heat insulation material: Polyethylene foam with thickness more than 8 mm (5/16 inch).
U-trap is not required for low static model in which the
external static pressure is below 50 pa(5mm Aq)
Pipe clamp
Maintenance
drain port
Indoor unit
Upward
routing
not allowed
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
Make sure to be closed.
Drainage conduit
Содержание AMNW07GSJL0
Страница 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 08B Replaces 0CTI5 08A P No MFL67502513 ...
Страница 2: ...MULTI SINGLE Indoor unit General information Product data ...
Страница 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...
Страница 34: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 1 5 Wiring Diagrams Deluxe AMNW07GSJL0 DM07RP NSJ ...
Страница 142: ...7 MULTI SINGLE Indoor unit Wall Mounted Unit 4 5 Wiring Diagrams ZJNW30GRLA1 US30F NR0 ZJNW36GRLA1 US36F NR0 ...
Страница 203: ...5 MULTI SINGLE CAC Indoor unit ART COOL 3 Dimensions ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...
Страница 205: ...7 MULTI SINGLE CAC Indoor unit ART COOL 5 Wiring Diagrams Models ZMNW09GAF10 MA09R NF1 ZMNW12GAF10 MA12R NF1 ...