18
g.
Complete installation of the cable gland. Once secure, tighten the T25 screws on the
adjustable rodent guard bracket to secure it in place. Multiple screw holes are available to fasten
the bracket at different heights.
7.
Strip each wire end 25 mm (1 in).
8.
Bundle the strands of each wire
tightly. DO NOT remove strands to fit the wire into the terminal.
9.
Connect the L1, L2, L3, and GND
(protective earth) service wiring to the
terminal block. Check local code to see
if Neutral is needed. Neutral
connection is not required for service
equipment operation and the terminal
is provided for convenience only.
To connect each wire:
a.
Fully insert the supplied Wago tool
into the Wago port (a) and rotate the
tool firmly counter-clockwise 90
o
to
open the connector.
b.
Lock the connector in the open
position by firmly pressing the orange
button below it (b).
c.
Insert the wire fully until it hits the
connector’s back stop.
d.
Insert and rotate the Wago tool
counter-clockwise again to close the
connector. The connector clicks as it
closes onto the wire and the orange
button is released.
CAUTION:
Stripping the wire
less
than 25 mm (1 in) can prevent the
Wago port from adequately
securing the wire.
This can cause
arcing or a similar electrical
hazard that could result in
property damage, injury, or
death.
CAUTION:
Ensure the exposed wires are tightly bundled with no loose strands. Loose or
missing strands
can cause arcing or a similar electrical hazard that could result in property
damage, injury, or death.
25 mm
(1 in)
N L1 L2 L3 GND