Device parameters and interfaces
Leuze electronic
BPS 34
69
TNT 35/7-24V
8.1.7.14 Module 13: Min/Max position
Notice!
Underlined in the CR column are the modules which must be activated in addition to the cur-
rent module.
Description
The Min/Max position function monitors the position value and transfers the maximum/
minimum value to the PROFIBUS master.
The acquisition time can be adjusted by means of two different modes:
• The "all values" mode detects all values since the start of measurement or since a
reset event.
• The "in measurement value window only" mode only detects extreme values which
occur in the time period defined in the "MinMax period" parameter.
Parameter
Hex coding of module 13 "Min/Max position"
The value listed in the table shows the hex coding of the default settings.
Parameter
Description
Rel.
addr.
Data
type
Value range
Default
Unit
CR to
module
MinMax
mode
Parameter activates Min/Max
evaluation function.
0
unsign
8
0: Off
1: All values
2: In measurement value
window only
0
–
–
MinMax
period
Defines the measurement value
window for the min-max values.
1
unsign
8
0 … 255
10
Measure-
ments
–
Parameter length: 2 byte
a
b
Internal ad
dress
of mod
u
le 13
MinMax mode
ad
dress 0
MinMax period
ad
dress 1
0C
00
0A