8.1
PROFIBUS
8.1.1
General information
The BPS 34 with MS 34 103/MS 34 105 is designed as a PROFIBUS device (PROFIBUS
DP-V0 acc. to IEC 61784-1) with a baud rate of 12 MBd. The functionality of the device is
defined via parameter sets which are clustered in modules. These modules are contained in
a GSE file. The
GSE file
can be downloaded from the Leuze Homepage at
www.leuze.de
-> under the heading Download -> Logistics -> Optical barcode positioning
. By using
a user-specific project tool, such as, e.g., Simatic Manager for the Siemens programmable
logic control, the required modules are integrated into a project during commissioning and
its settings and parameters are adjusted accordingly. These modules are provided by the
GSE file.
All input and output modules described in this documentation are described from the
controller's perspective:
• Input data arrives at the controller
• Output data are sent out by the controller.
8.1.2
Electrical connection
Figure 8.1:Electrical connection of PROFIBUS connections DP IN and DP OUT
Socket
(A-coded)
Socket
(A-coded)
Socket
(B-coded)
Plug
(B-coded)
Plug
(A-coded)
DP IN
GND 3
2
1
4
PE
A (N)
B (P)
VCC
DP OUT
VCC 1
2
3
4
A (N)
B (P)
GND
PE
PWR IN
SWIN
SWOUT
3
2
1
4
GND
VIN
PE
SW IN/OUT
1
2
3
4
VOUT
PE
SWIN
SWOUT
GND
1
2
3
4
MSD
5
6
7
/SERV
VIN
TXD
RXD
SCL
SDA
GND
/INT