Device parameters and interfaces
Leuze electronic
BPS 34
67
TNT 35/7-24V
Hex coding of module 11 "Measurement value preparation"
The value listed in the table shows the hex coding of the default settings.
Input data
none
Output data
Notice!
The BPS 34 is set as follows by default:
The position value is output with "normal" count direction. With the "inverted" count direction,
10’000’000 mm minus the position value is output. This behaviour can be influenced using
the "Static preset"/"Dynamic preset" modules (module 3 and module 4, respectively) and
the "Offset" module (module 5).
Figure 8.12: Count direction for position calculation
Internal ad
dress
of module 11
Integration depth
ad
dress 0
05
00 08
Output
data
Description
Rel.
addr.
Data
type
Value range
Default
Unit
CR to
module
Count
direction
Count direction for position cal-
culation
0.0
Bit
0: Normal
: Inverted
0
–
–
Output data length: 1 byte
b
Count direction "normal"
Count direction "inverted"
Position value = tape value
Position value
Count direction
Count direction
1’400’000 mm
8’600’000 mm (=10’000’000 mm - tape value)
0 mm
10’000’000 mm
0 mm
10’000’000 mm