45
TNT 35/7-24V
8.1.3
PROFIBUS address
In the modular hoods with integrated connectors MS 34 103 and MS 34 105, the
PROFIBUS address can be set via two rotary switches and one slide switch.
The configuration and function of the address switches is shown in figure 8.4.
Figure 8.4:Setting the PROFIBUS address in the MS 34 103/MS 34 105
8.1.4
General information on the GSE file
You can find the GSE file at
www.leuze.de -> Download -> Logistics -> Optical barcode
This file stores all the data required for the operation of the BPS 34. This data consists of
device parameters required for operation of the BPS 34 and the definition of the control and
status bits. If parameters are changed in the project tool, for example, these changes are
stored in the project, not in the GSE file.
The GSE file is part of the device and must not be changed manually. The file is not changed
by the system either.
If the BPS 34 is operated in a PROFIBUS network, configuration must be performed exclu-
sively via the PROFIBUS. The functionality of the BPS 34 is defined via GSE parameter
sets. The parameters and their functions are structured in the GSE file using module. A user-
specific configuration tool is used during PLC program creation to integrate the required
modules and configure them appropriately for their respective use.
During operation of the BPS 34 on the PROFIBUS, all parameters are set to default values.
If these parameters are not changed by the user, the device functions with the default
settings delivered by Leuze electronic. For the default settings of the BPS 34, please refer
to the following module descriptions.
Notice!
A least one module in the GSE file must be activated in the configuration tool for the control,
usually the "Position value" module 1.
Slide switch for the hundreds (marked with 10
2
)
Rotary switch for the tens (marked with 10
1
)
Rotary switch for the single digits (marked with 10
0
)
Connector to the BPS 34
Position of the slide
switch
:
Top
address
100 - 126
Bottom
address
1 - 99