PWR IN - voltage supply and switching input/output
Attention!
For devices with integrated heating, the supply voltage must be wired with a minimum
0.5 mm² (recommended 0.75 mm²) core cross section. It is not possible to loop the
supply voltage through to other loads!
Notice!
Cables with a core cross section of 0.5 mm² or 0.75 mm² are not available as ready-made
cables from Leuze electronic.
Figure 4.4:
Pin assignment PWR IN
Connection of the functional earth PE
BPS 34 including hood with integrated connectors MS 34 103/MS 34 105:
!
Connect
PE
to
PIN 5 of the M 12 connector
PWR IN
for the voltage supply!
Notice!
Programming of the switching input/switching output is performed via module 7 (Switching
input) and module 8 (Switching output). For further information, see also chapter 8.1.7.7,
page 59 ff.
Notice!
The switching input/switching output of the
PWR IN
plug connection is identical to the
SWIN
switching input and
SWOUT
switching output of the
SW IN/OUT
plug connection on the
MS 34 105.
Attention!
Protection class IP 65 is achieved only if the connectors and caps are screwed into place!
PWR IN (5-pin plug, A-coded)
Pin
Name
Remark
1
VIN
Positive supply voltage
without optics heating: +10 … +30 V DC
with optics heating: +22 … +26 V DC
2
SWOUT Switching output
3
GND
Negative supply voltage 0 V DC
4
SWIN
Switching input
5
PE
Functional earth
Thread
PE
Functional earth (housing)
PWR IN
SWIN
SWOUT
3
2
1
4
GND
VIN
PE
M 12 plug
(A-coded)