Starting up the device - Configuration
Leuze electronic
BCL 604i
88
Parameter length
23 byte
Input data
None
Output data
None
Comment
The DC bias level also defines whether the output is low-active (0) or high-active (1).
Switching on an I/O configured as an output means switching to the active state; switching off, on the other
hand, results in switching to the inactive or idle state.
10.12.7Module 72 – Switching input/output SWIO3
Parameter
Table 10.50:
Parameters for module 72 – Input/Output 3
Compare mode
(Event Counter)
Specifies whether the switching output
switches only on parity (once) or also in the
event of greater or equal to (multiple times)
after the comparative value is reached.
11
UNSIGNED8
0: SWOUT switches once
1: SWOUT switches sev
-
eral times
0
-
Reset mode
(Event Counter)
Specifies whether the counter (Event Counter)
is reset only by the reset bit and the selected
switch-off function, or if the counter should be
automatically reset after the comparative value
is reached.
12
UNSIGNED8
0: Reset bit and switch-off
funct.
1: Comparative value
reached
0
-
Mode of operation for configuration as an input
Inversion
The parameter defines the logic of the incident
signal. In case of an inversion, an external
HIGH level is interpreted internally as a LOW
level.
13.1
Bit
0: Normal
1: Inverted
0
-
Reserved
Free
13.2 … 13
.7
Debounce time
The parameter defines a debounce time which
is implemented in software.
14
UNSIGNED16 0 … 1000
5
ms
Start-up delay
The parameter influences the timing during
switch-on.
16
UNSIGNED16 0 … 65535
0
ms
Minimum switch-
on time
The parameter defines a minimum time period
before the signal is reset.
18
UNSIGNED16 0 … 65535
0
ms
Delay off time
The parameter defines a time delay for the sig
-
nal during switch-off.
20
UNSIGNED16 0 … 65535
0
ms
Input function
The parameter specifies the function which is
to be activated or deactivated by a change of
state in the signal.
22
UNSIGNED8
0
-
Parameter
Description
Addr.
Data type
Value range
Default
Unit
Parameter
Description
Addr.
Data type
Value range
Default
Unit
Function
This parameter defines whether I/O 3 func
-
tions as an input or as an output.
0.0
Bit
0: Input
1: Output
0
-
Mode of operation for configuration as an output
DC bias level
The parameter defines the DC bias level of the
switching output and, thus, simultaneously
whether the output is low-active (0) or high-
active (1).
0.1
Bit
0: LOW (0V)
1: HIGH (+Ub)
0
-
Reserved
Free
0.2 … 0.7
Start-up delay
With this parameter, the output pulse may be
delayed by a set time period.
1
UNSIGNED16 0 … 65535
0
ms