Commissioning and configuration
Leuze electronic
BCL 548
i
171
TNT
35/7-2
4
V
10.12 Device Functions
10.12.1 Module 60 – Device status
PROFINET-IO module identifier
Module-ID 1060
Submodule-ID 1
Description
The module contains the display of the device status as well as control bits for triggering a
reset or putting the device into standby mode.
Parameter
None
Input data
Input data length
1 byte
Output data
Notice!
Analogous to command H, activation of the system reset bit triggers a restart of all electron-
ics, incl. a restart of the PROFINET-IO stack. I.e. the device restarts.
Output data length
1 byte
Notice!
When resetting the data (see Module 10 – Activations), the input data of this module is not
deleted.
Input data
Description
Addr.
Data type
Value range
Init value Unit
Device status
This byte represents the
device status
0
UNSIGNED8
0:
Device is ready
1: Initialization
10:
Standby
11:
Service
12:
Diagnosis
13:
Parameter enabled
15:
Device is ready
0x80:
Error
0x81:
Warning
0
-
Table 10.35:
Input data for module 60
Output data
Description
Addr.
Data type
Value range
Init value Unit
System reset
The control bit triggers a system reset
if the level changes from 0 to 1
0.6
Bit
0:
Run
0 -> 1: Reset
0
-
Standby
Activates the standby function
0.7
Bit
0: Standby off
1: Standby on
0
-
Table 10.36:
Output data for module 60