Display and control panel AMS 358i
Leuze electronic
AMS 358
i
46
TNT
35/7-2
4
V
Notice!
The rear cover
of this manual includes a
fold-out page
with the complete
menu structure
.
It describes the menu items in brief.
8.3.2
Parameter menu
Parameter handling submenu
The following functions can be called up in the
Parameter handling
submenu:
• Lock and enable parameter entry
• Set up a password
• Reset the AMS 358
i
to default settings.
Additional important information on parameter handling can be found at the end of the
chapter.
EtherNet/IP submenu
Table 8.1:
Parameter handling submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Parameter
enabling
ON / OFF
The standard setting (
OFF
) prevents unintended parameter changes.
With parameter enabling activated (
ON
), the display is inverted. In this
state, it is possible to change parameters manually.
OFF
Password
Activate
password
ON / OFF
To enter a password, parameter enabling must be activated.
If a password is assigned, changes to the AMS 358
i
can only be made
after the password is entered.
The master password 2301 bridges the individually set password.
OFF
Password
entry
Configuration option of a four-digit numerical password.
Parameters to
default
By pressing the enter button
after selecting
Parameters to default
, all parameters are reset to their
standard settings without any further security prompts.
In this case, English is selected as the display language.
Table 8.2:
EtherNet/IP submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Activation
ON / OFF
EtherNet
interface
Address
Address
The IP address can be set to any value in the ---.---.---.--- format.
Normally, the network administrator specifies the IP address that is to be
set here. If DHCP is activated, the setting made here has no effect and
the AMS 358
i
is set to the values that it obtains from the DHCP server.
Gateway
The gateway address can be set to any value in the
---.---.---.--- format.
The AMS 358
i
communicates with participants in other subnets via the
gateway. Splitting the read application over multiple subnets is rather
uncommon; the setting of the gateway address, thus, usually has no
meaning.