Display and control panel AMS 358i
Leuze electronic
AMS 358
i
42
TNT
35/7-2
4
V
8.2.2
LED status displays
After power ON, a test of the Power LED and Net LED is performed in the following sequence:
1.
LEDs off.
2.
LEDs are switched to green for approx. 0.25 s.
3.
LEDs are switched to red for approx. 0.25 s.
4.
LEDs off.
This is followed by the status display for the power LED (see chapter 9.3) and the Net LED.
PWR LED
Off
Device OFF
- No supply voltage
Flashing green
Power LED flashes green
- LED function test for 0.25 s after power up
- No measurement value output
- Voltage connected
- Self test running
- Initialization running
- Parameter download running
- Boot process running
Green continuous light
Power LED green
- AMS 358
i
ok
- Measurement value output
- Self test successfully finished
- Device monitoring active
Red flashing
Power LED flashes red
- LED function test for 0.25 s after power up
- Device ok but warning message (ATT, TMP, LSR)
set in display
- Light beam interruption
- Plausibility error (PLB)
Red
continuous light
Power LED red
- No measurement value output; for details, see
Display