Display and control panel AMS 335i
44
AMS 335
i
Leuze electronic
Additional important information on parameter handling can be found at the end of the
chapter.
CANopen submenu
Position value submenu
Notice!
The parameters named under position value are to be set via the EDS file of the AMS 335
i
.
If parameters from the position value submenu are changed via the display, these may be
overwritten via a startup sequence stored in the control.
Password
Activate
password
ON / OFF
To enter a password, parameter enabling must be activated.
If a password is assigned, changes to the AMS 335
i
can only be made
after the password is entered.
The master password 2301 bridges the individually set password.
OFF
Password
entry
Configuration option of a four-digit numerical password
Parameters to
default
By pressing the enter button
after selecting
Parameters to default
, all parameters are reset to their stan-
dard settings without any further security prompts.
In this case, English is selected as the display language.
Table 8.2:
CANopen submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Activation
ON / OFF
ON
Node ID
Value range 1 - 127
1
Baud rate
20kbit/s / 50kbit/s / 125k/bit/s / 250k/bit/s / 500k/bit/s /
800k/bit/s /1000k/bit/s
Selection of the baud rate for serial communication. The baud rate spec-
ifies the speed of data transmission. It must be the same at the transmis-
sion and reception sides to enable communication.
125kbit/s
Position resolu-
tion
0.01mm / 0.1mm / 1mm / 10mm / free resolution
The measurement value can be displayed in these resolutions.
The value of the free resolution is determined in the "Position value" sub-
menu in the "Value of free resolution" parameter.
1mm
Velocity resolu-
tion
1mm / 10mm / 100mm / 1000mm / free resolution
The current velocity can be displayed in these resolutions.
The value of the free resolution is determined in the "Velocity value" sub-
menu in the "Value of free resolution" parameter.
1mm/s
Table 8.1:
Parameter handling submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard