CANopen interface
Leuze electronic
AMS 335
i
67
TNT
35/7-2
4
V
Preset value and offset value are not offset against each other. The resolution of the offset
value is independent of the position value resolution selected. The offset value is active
immediately without any further release.
Sub-index 06 free resolution
Free resolution in mm/1000 or inch/100000, in accordance with the unit selected.
The "free resolution" parameters from sub-index 03 and the "value free resolution" from
sub-index 06 are mutually dependent. The value of the free resolution is multiplied by mm/
1000 or inch/100000 in accordance with the unit selected. The multiplication product is then
the free resolution that has been set.
9.5.8.2
Object 2001
h
Static preset value
The static preset value is a parameter that is not changed after the handover of the system
to the end user. It is configured during commissioning and remains unchanged thereafter.
A preset value can be entered into the object. The preset value is activated with "preset
teach" and deactivated with "preset reset". After preset teach, the current position value is
offset against the configured preset value. After preset reset, the original measurement value
is displayed.
9.5.8.3
Object 2002
h
Dynamic preset value
The dynamic preset value can be adapted permanently via the control.
The dynamic preset value is activated with "preset teach" and deactivated with "preset
reset". After preset teach, the current position value is offset against the configured preset
value. After preset reset, the original measurement value is displayed.
Index
Sub-
index
Name
Data type
Access
Value range
Remark
(hex)
(hex)
Minimum
Maximum
Default
2001
01
Preset value
static
int 32
rw
-999999
999999
0
Preset value, in mm
or in/100 depend-
ing on the unit
selected
02
Preset
settings
u 8
rw
0
2
0
Value 1 =
preset teach
Value 2 =
preset reset
Index
Sub-
index
Name
Data type
Access
Value range
Remark
(hex)
(hex)
Minimum
Maximum
Default
2002
01
Preset value
static
int 32
rw
-999999
999999
0
Preset value, in mm
or in/100 depend-
ing on the unit
selected
02
Preset
settings
u 8
rw
0
2
0
Value 1 =
preset teach
Value 2 =
preset reset