NOTICE
▶
UL marking
▶
Internal overload protection rated for 125 % of the rated FLA.
▶
Marquage UL
▶
Protection contre les surcharges conçue pour se déclencher à 125 % de l'intensité assignée à pleine
charge.
Fusing data
Branch Circuit Protection (BCP)
Short Circuit Current Ratings (SCCR) with Standard Fuses and Circuit Breaker
(Tested per UL61800-5-1, reference UL file E132659)
These devices are suitable for motor group installation when used with Standard Fuses or Circuit Breaker.
For single motor installation, if the fuse value indicated is higher than 400 % of the motor current (FLA), the
fuse value has to be calculated. If the value of the fuse is below two standard ratings, the nearest standard
ratings less than the calculated value shall apply.
Inverter
Standard Fuses (UL248)
Circuit Breaker (UL489)
Mains
Rated power
SCCR
Max. rated current
Class
SCCR
Max. rated current
kW
HP
kA
A
kA
A
120 V, 1-ph
0.37
0.5
5
30
CC, CF, J, T
5
30
120 V, 1-ph
0.75
1
5
30
CC, CF, J, T
5
30
230 V, 1/3-ph
0.37
0.5
42
25
CC, CF, J, T
5
230 V, 1/3-ph
0.75
1
42
25
CF, J, T
5
230 V, 1/3-ph
1.1
1.5
42
25
CF, J, T
5
230 V, 1/3-ph
1.5
2
42
25
CF, J, T
5
230 V, 1/3-ph
2.2
3
42
50
CF, J, T
5
30
230 V, 3-ph
3
4
42
60
CF, J, T
5
30
230 V, 3-ph
4
5
42
60
CF, J, T
5
30
480 V, 3-ph
0.75
1
65
50
CF, J, T
5
30
480 V, 3-ph
1.1
1.5
65
50
CF, J, T
5
30
480 V, 3-ph
1.5
2
65
50
CF, J, T
5
30
480 V, 3-ph
2.2
3
65
50
CF, J, T
5
30
480 V, 3-ph
3
4
5
40
CF, J, T
5
30
480 V, 3-ph
4
5
5
40
CF, J, T
5
30
480 V, 3-ph
5.5
7.5
5
40
CF, J, T
5
30
Electrical installation
Connection according to UL
Fusing data
23