EDS84DMOTPBUS EN 3.0 - 11/2011
L
31
Communication manual 8400 motec PROFIBUS
Commissioning
Possible settings via DIP switch
6.3.2
Setting the station address
If there are several networked PROFIBUS stations, the station addresses must differ from
each other.
The station address can be set via the DIP switches
1 ... 64
or via the »Engineer« with code
If the station address is to be set via
, the DIP switches
1 ... 64 must be set to OFF
.
DIP switch settings
The package labelling indicates the valencies of the individual DIP switches for setting the
station address.
Example:
The current address set with the switches is displayed in
.
The station address active at the PROFIBUS is displayed in
.
DIP switch positions for setting the station address
Note!
• The valid address range is 0 ... 126 (max. 125 slaves).
• If all
DIP switches 64 ... 1 = ON
, the address saved last will be used.
DIP switch
Station address
S
64
32
16
8
4
2
1
OFF
...
...
...
...
...
...
...
Autom. via master
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Value from
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
1
ON
...
...
...
...
...
...
...
...
ON
ON
ON
ON
ON
ON
ON
OFF
126
ON
ON
ON
ON
ON
ON
ON
ON
Address saved last
DIP switch
64
32
16
8
4
2
1
Switch position
OFF
OFF
ON
OFF
ON
ON
ON
Value
0
0
16
0
4
2
1
Station address
= sum of the valencies = 16 + 4 + 2 + 1 = 23