Communication manual 8400 motec PROFIBUS
Parameter reference
Parameters relevant for PROFIBUS communication
C13866
C13867
C13880
C13881
Parameter | Name:
C13866 | Display: Most recent CFG data
Data type: OCTET_STRING
Index: 10709
d
= 29D5
h
Display of the last configuration data sent by the PROFIBUS master with the "Chk-Cfg" telegram (ASCII string with
22 characters)
;
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13867 | Display: Most recent diagnostic data
Data type: OCTET_STRING
Index: 10708
d
= 29D4
h
Display of the last diagnostic data sent to the PROFIBUS master (ASCII string with 16 characters)
;
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13880 | Reaction on communication failure
Data type: UNSIGNED_8
Index: 10695
d
= 29C7
h
Monitoring response to a communication fault on the PROFIBUS
• A change in the monitoring response is effective immediately.
Permanent interruption of PROFIBUS communication (
Selection list
0 No response
1 Error
4 Warning locked
Subcodes
Lenze setting
Info
C13880/1
0: No response
The response set here for the "watchdog/data exchange"
monitoring is executed if the bus station ...
• does not receive a message from the master within
the watchdog monitoring time (during an active
connection displayed under
• detects that it is no longer in the "Data_Exchange"
state. Please see also the notes given under
.
;
Read access
;
Write acces
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13881 | Monitoring time: Data exchange
Data type: UNSIGNED_16
Index: 10694
d
= 29C6
h
If the "Data_Exchange" state has been exited, the response parameterised with
monitoring time set here for the data exchange has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change in monitoring is effective immediately.
• The value set here for the monitoring time must be smaller than the watchdog monitoring time (displayed under
Permanent interruption of PROFIBUS communication (
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
65535
65535 ms
;
Read access
;
Write acces
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT