Communication manual 8400 motec PROFIBUS
Parameter reference
Parameters relevant for PROFIBUS communication
88
L
EDS84DMOTPBUS EN 3.0 - 11/2011
C13920
C13950
Parameter | Name:
C13920 | Display: DIP switch setting
Data type: UNSIGNED_8
Index: 10655
d
= 299F
h
Display of the current DIP switch setting
• The displayed value corresponds to the sum of the individual DIP switch values 1 ... 64.
• The active station address is displayed under
Display area
(min. value | unit | max. value)
0
255
;
Read access
Write access
CINH
PLC-STOP
;
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13950 | Module internal communication status
Data type: UNSIGNED_8
Index: 10625
d
= 2981
h
Display of the internal status of the communication unit
Selection list
(read only)
Info
0 Not initialized
1 Module ready for initialization
2 Reading Module parameters
3 Module Parameters has been read
4 Initialization of external protocol
5 Online
6 Module timeout
;
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Содержание E84DGFCp Series
Страница 2: ...2 L EDS84DMOTPBUS EN 3 0 11 2011 ...