Error codes (object dictionary 2007
h
or 2017
h
- Errorcode)
Error Code (hex)
Cause
Comment
Effect
Corrective Action
e.g. 0x0291
Cross-fault at or external power supplied to input
Cross-fault to another input or
test pulse output or external
power supplied; red diagnosis LED
of affected channel lights up.
Inputs and outputs turn "0" at the
module and in the process map.
Module in safe state
Check sensor
Check test pulse outputs
Check connector and wiring
0x0291
Short circuit or overload
Short circuit in the output wiring
or wrong output load, red
diagnosis LED of affected channel
lights up
Module in safe state
Check actuator
Check connector and wiring
Check free wheel wiring at contactor
0x0280
Cross-fault at or external power supplied to output
Cross-fault to another output or
another signal; red diagnosis LED
of affected channel lights up
Module in safe state
Check actuator
Check connector and wiring
Information
For a detailed description of the entry in object 2007h or 2017h "Errorcode",
refer to the table in section 0.
6.5.8
EtherCAT Link Lost
All modules change to their safe state when the EtherCAT link is lost or interrupted. Once the
fault has been removed, an Error Acknowledge is enough to restart the EtherCAT bus.