6
Installation
and Operation
EDBC250SIO | 2.0
173
Allocation of safe outputs to the test pulse outputs
CAUTION
Do not use two inputs with the same test pulse signal for any one safety func-
tion
Faulty wiring will not be detected.
The inputs used for a safety function must not be supplied power from the
same test pulse output.
Correct example: Use SI0 with SI 0/4 TP and SI1 with SI 1/5 TP for the same
safety function.
Incorrect example: Use SI0 with SI 0/4 TP and SI4 with SI 0/4 TP for a safety
function. (Impermissible!)
Allocation of safe inputs to the test pulse outputs (Safety I/O-module SDI16 and Safety I/O-
module SDI16 SDO4 0.5A):