4
Product Description
EDBC250SIO | 2.0
24
4.5.4
Safe Digital Outputs
Safe digital outputs
Quantity and type
2x semiconductor, 24 VDC, tolerance to EN 61131-2:2007
Max. safety levels
2x cat. 3/PL e to EN ISO 13849-1:2015,
2x SIL3 to EN 62061:2010,
2x SIL3 to IEC 61508:2010
Diagnosis
cross-fault, external power supply
Signal indication
LED located next to the terminal, controlled by CPU
Minimum output current
2 mA, see
►
6.2.8 Actuator Connection for details
Maximum output current
2,0 A, short-circuit-proof, comply with total load and derating
See section
►
6.2.8 Actuator Connectionfor - Derating of Total Load for details
Capacitive load
yes, see section
►
6.2.8 Actuator Connectionfor - switching of capacity loads
for details
Braking voltage while turning off
inductive loads
typ. 40 VDC
Inductive load
yes, see section
►
6.2.8 Actuator Connection - switching of inductive loads for
details
Maximum line length
100 m (between sensor / module terminals)
Response threshold of output
overload protection
min. 2.5 A
typ. 3.5 A
max. 5.5 A
Output current modulemax
4 A, comply with total load and derating See section
►
6.2.8 Actuator
Connectionfor - Derating of Total Load for details
Load resistance range (at nominal
voltage)
12 Ω ... 12 kΩ
Electrical insulation
channel/channel: no
channel/E-bus: 500 Veff
Approved actuators
DC 13 to EN60947-5-1 Table 4
DC 1 to EN60947-4
Duration of test impulse
configurable: 500 µs ... 1500 µs (configurable)
Supply voltage
24 VDC -15%/+20%
Electric strength
33 V (max. voltage to output even in case of error)
Содержание c250-S
Страница 51: ...6 Installation and Operation EDBC250SIO 2 0 51 6 2 6 Power Supply Wiring Example ...
Страница 263: ......