8
Appendix
EDBC250SIO | 2.0
241
Note, information
The temperature value is not intended for safety-related evaluation.
Do not use in safety functions!
8.1.13
Errorcode 2007
h
for CPU1 and 2017
h
for CPU2
Designation
Value
Name
Errorcode
Index
2007
h
/ 2017
h
Object Code
VARIABLE
No. of Elements
0
Data Type
UNSIGNED16
Access
Read only
PDO Mapping
No
Default Value
0000
h
The table below explains the entries in object 2007
h
or 2017
h
"Err.code".
Id
Hex
Explanation
0
0x0000
OK
No error
1
0x0001
HWT_PARAMETER_ERROR
Test library: Parameter Error
2
0x0002
HWT_INIT_ERROR
Test library: Initialisation Error
100
0x0064
HWT_MEM_MARCHC_ERROR
Test library: Error RAM Test
101
0x0065
HWT_MEM_GALPAT_ERROR
Test library: Error RAM Test
200
0x00C8
HWT_STACK_UNDERFLOW_ERROR
Test library: Underflow Error
201
0x00C9
HWT_STACK_OVERFLOW_ERROR
Test library: Overflow Error
300
0x012C
HWT_CPU_ERROR
Test library: CPU Test Error
400
0x0190
HWT_FW_ERROR
Test library: FW Error
500
0x01F4
HWT_FWINTERFACE_ERROR
Test library: FW Interface Error
504
0x01F8
HWT_ADC_ERROR
Test handler: Error in ADC value range checks
505
0x01F9
HWT_DMA_ERROR
Test handler: Error in DMA check
506
0x01FA
HWT_CRC_ERROR
Test handler: Error in CRC check
507
0x01FB
HWT_TIMER_ERROR
Test handler: Error in timer check
508
0x01FC
HWT_CLOCK_ERROR
Test handler: Eerror in clock signal check
509
0x01FD
HWT_SOFTERROR
Soft error detected
510
0x01FE
HWT_DIVZERO
Division by 0
544
0x0220
INIT_ERROR
Initialisation error
576
0x0240
TIMEOUT_ERR
I2C communication timeout detected
578
0x0242
TIMEOUTTIMERERR
Timeout occurred
579
0x0243
POWERUP_TIMEOUT
Timeout occurred while waiting for valid supply volt-
age values during power up
I
Содержание c250-S
Страница 51: ...6 Installation and Operation EDBC250SIO 2 0 51 6 2 6 Power Supply Wiring Example ...
Страница 263: ......