6.2.1
Mounting Position
Lenze Safety I/O-module mount on 35 mm rails to DIN EN 50022. Mount the rail horizontally
and make sure that the modules' multiple socket connectors are pointing away from the wall.
To ensure that enough air gets in through the ventilation slots, leave at least 20 mm to the top
and 35 mm to the bottom of a module and any adjacent devices or cabinet surfaces. Leave at
least 20 mm of lateral distance to third-party units and cabinet surfaces.
CAUTION
Do not operate the Safety I/O-module module out of the specified range
Faults by component overload caused by excessive temperature
Operate the module under the ambient conditions listed in section Technical
Data only while observing the derating of the outputs – see
►
section 6.3.10.