Electrical installation − HighLine/StateLine version
Communication
99
EDS84DPS424 EN 5.0
6.7
Communication
Carry out the installation in accordance with the mounting directives of the fieldbus
systems in order to prevent a faulty communication. Please observe the notes on the
additional equipotential bonding.
Stop!
High compensation currents
High compensation currents can flow via the shield of the fieldbus cable.
Possible consequences:
Damage to material assets or failures
Protective measures:
Prevent compensation currents via the shield of the fieldbus cable as follows:
ƒ
Connect all fieldbus nodes with a 16 mm
2
cable via the earthing studs.
ƒ
Lay this cable in parallel to the bus cable.
ƒ
Ensure a highly conductive connection of all earthing studs with a copper
braid cable to the mounting surface.
E84DWX0003
Earthing for compliance with EMC conditions, prevents compensation currents via the
shield of the fieldbus cable
16 mm
2
equalizing conductor with ring cable lug M6
The communication cables of the available fieldbus systems can be installed using
different plug versions. The type code provides information on the design of one device.
Содержание 8400 protec
Страница 2: ...0Fig 0Tab 0...
Страница 189: ...Appendix Declarations and certificates 13 189 EDS84DPS424 EN 5 0 13 Appendix 13 1 Declarations and certificates...
Страница 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Страница 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Страница 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Страница 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Страница 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...