Electrical installation − HighLine/StateLine version
Important notes
6
73
EDS84DPS424 EN 5.0
6
Electrical installation − HighLine/StateLine version
6.1
Important notes
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Switch off the power supply and wait for at least three minutes before
working on the power terminals.
ƒ
Make sure that all power terminals are deenergised.
Danger!
ƒ
The contacts of the power connectors
X10, X11, X20 and X21
may carry
dangerous voltage if the frequency inverter is connected to the mains. Thus,
deenergise the frequency inverter before working on it.
ƒ
Earth the device by means of X10 and by connecting it to functional earth
(earthing bolt) in order to prevent injury to persons and malfunctioning.
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when the device is touched in the event of a fault.
Protective measures:
ƒ
Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
10 mm
2
or PE conductor must be connected twice)
Содержание 8400 protec
Страница 2: ...0Fig 0Tab 0...
Страница 189: ...Appendix Declarations and certificates 13 189 EDS84DPS424 EN 5 0 13 Appendix 13 1 Declarations and certificates...
Страница 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Страница 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Страница 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Страница 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Страница 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...