Electrical installation − HighLine/StateLine version
Devices in a power range of 0.75 ... 7.5 kW (3/PE AC 400 V)
Terminal assignment of the power connections
90
EDS84DPS424 EN 5.0
Stop!
Damage of the devices
A defective motor holding brake or a short circuit on the X21 connection
(motor and built−on accessories) causes internal damage to the device.
Possible consequences:
ƒ
If a defective motor holding brake is connected, the replacement device is
also damaged immediately.
Protective measures:
ƒ
When devices are replaced due to malfunction of the brake control, ensure
that defect−free motor holding brakes are connected.
ƒ
Check whether the motor holding brake and the connecting cable are free
from defects.
ƒ
Replace or repair defective components.
Note!
In the Lenze setting, the temperature monitoring of the motor is activated! To
start motors without thermal detectors, the response of the motor
temperature monitoring must be deactivated (C00585). Alternatively, a wire
jumper bPTC and −PTC can be used to simulate a normal
temperature.
Содержание 8400 protec
Страница 2: ...0Fig 0Tab 0...
Страница 189: ...Appendix Declarations and certificates 13 189 EDS84DPS424 EN 5 0 13 Appendix 13 1 Declarations and certificates...
Страница 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Страница 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Страница 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Страница 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Страница 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...