Technical data
Control terminals
Interfaces of the EMS version
67
EDS84DPS424 EN 5.0
4.7.6
Interfaces of the EMS version
CANopen Master PLC
X34
Pin / Name
Features
Rated value
1 /
Shielding (functional earth)
−
2 / n. c.
not assigned
−
3 / CAN_GND
CAN GND
Bit rate: adjustable up to 1 Mbit
Isolation: Function separation
4 / CANH
CAN HIGH
5 / CANL
CAN LOW
RS485/422 PLC
X81/X82
Pin / Name
Features
Rated value
RS485
RS422
The
assignment
depends on the
device version
(
24 V supply
according to IEC 61131−2, type 1
RS485A’
Rec (Data+)
according to:
– ANSI/TIA/EIA−485−A−98
– ANSI/TIA/EIA−422
Bit rate: Adjustable up to 115.2 kbit
Isolation: Function separation
At RS422, PLC supports evaluation of SSI
encoders (max. 150 kHz).
RS485B’
Reception (Data−)
RS485A
Trans (CLK+)
RS485B
Transmission− (CLK−)
Infrared interface (IrDA)
IrDA (Infrared Data Association)
Pin / Name
Features
Rated value
−
Reach
~1 m
Angle of incidence
~30 °
Содержание 8400 protec
Страница 2: ...0Fig 0Tab 0...
Страница 189: ...Appendix Declarations and certificates 13 189 EDS84DPS424 EN 5 0 13 Appendix 13 1 Declarations and certificates...
Страница 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Страница 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Страница 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Страница 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Страница 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...