![Lenze 8200 vector E82CV153K4B Скачать руководство пользователя страница 170](http://html1.mh-extra.com/html/lenze/8200-vector-e82cv153k4b/8200-vector-e82cv153k4b_mounting-instructions_1882275170.webp)
Commissioning
Parameter setting with E82ZBC keypad
Vector control
170
EDK82EV903 DE/EN/FR 5.1
7.2.2
Vector control
The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.
Switch−on sequence
Comment
1.
Connect keypad
2.
Ensure that controller inhibit is active after mains connection
Terminal X3/28 = LOW
3.
Switch on the mains
4.
5.
The keypad is in "Disp" mode after approx. 2 s and indicates the
output frequency (C0050)
The
USEr
menu is active
6.
Go to the
ALL
menu
7.
Change to the
mode to configure the basic settings for your
drive
Blinking on the display:
0050
8.
Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation
9.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
10.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
11.
Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
12.
Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
13.
Activate the operating mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
14.
Adapt the voltage/current range for the analog setpoint selection
(C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
Set the DIP switch on the standard I/O to the same
range (see Mounting Instructions for the standard
I/O)
15.
Enter the motor data
See motor nameplate
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
Enter the value for the motor circuit configuration
(star/delta) selected!
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
Enter the value for the motor circuit configuration
(star/delta) selected!
E
Motor cos
j
(C0091)
Lenze setting: Depending on the controller