Electrical installation
Standard devices in the power range of 55 kW
Mains connection
147
EDK82EV903 DE/EN/FR 5.1
5.4
Standard devices in the power range of 55 kW
5.4.1
Mains connection
Stop!
ƒ
Only connect the controller to the permitted mains voltage (
Technical
data). A higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
0
1
L1
L2
L3
N
PE
+UG
-UG
Z1
PE
L1
L2
L3
3/PE AC 400V
T2
T1
L2 L3
L1
2
3
3
3
3
4
4
L1 L2 L3
+UG
-UG
PE
l
3/PE AC 400V
PE
L1, L2, L3
+UG, -UG
PE
15 Nm
132 lb-in
M8
PE L1’
L2’
L3’
Gerät / Load
Z1
L1 L2 L3
+UG
-UG
PE
l
PE
L1, L2, L3
+UG, -UG
PE
15 Nm
132 lb-in
M8
T1
T2
2,5 Nm
22.1 lb-in
L1 L2 L3
+UG
-UG
3/PE AC 400V
PE
l
L1 L2 L3
+UG, -UG
PE
M8
15 Nm
132 lb-in
PE
E82EV453K4:
2-6 Nm (17.7-53.1 lb-in)
E82EV553K4:
6-12 Nm (53.1-106.2 lb-in)
L1, L2,
L3
J>
8200vec289
Connection for mains choke
Connection for footprint mains filter
Connection for built−on mains filter
Connection for braking unit (
Documentation of braking unit)
Temperature monitoring connection for mains filter (thermal contact)
Z1
Mains choke/mains filter