Electrical installation
Standard devices in the power range of 55 kW
Fuses and cable cross−sections according to EN 60204−1
148
EDK82EV903 DE/EN/FR 5.1
5.4.2
Fuses and cable cross−sections according to EN 60204−1
Supply conditions
Range
Description
Fuses
l
Utilisation category: only gG/gL or gRL
Cables
Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).
RCCB
l
Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a
fault current monitoring unit (RCM) is used for protection in the case of direct or indirect
contact, only one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a
1−phase system
Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system
by using a transformer.
l
Earth−leakage circuit breakers must only be installed between mains supply and controller.
Observe all national and regional regulations!
Operation with increased rated power
System Manual
Operation at rated power
8200 vector
Rated fuse current
Cable cross−section
FI
1)
Fuse
Circuit−breaker
Laying system L1, L2, L3, PE
B2
C
Type
[A]
[A]
[mm
2
]
[mm
2
]
[mA]
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV453K4B
Operation only permitted with mains choke or mains filter
E82xV553K4B
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV453K4B
100
−
−
35
³
300
E82xV553K4B
125
−
−
35
1)
Earth−leakage circuit breaker