background image

Page 22

If the burner is in the

below state:

Pushing the reset button will:

Button Click

(press < 1 second)

Button Hold

(press > 1 second)

Button Hold

(press 15+ seconds)

t

u

o

k

c

o

L

tf

o

S

m

o

r

f

t

e

s

e

R

t

u

o

k

c

o

L

Reset from Restricted 
(Hard) Lockout

Valve−on Delay, Trial for 
Ignition, Ignition Carryover

Go to pump prime (see 
Priming the Pump" above)

Disable the Burner:
Any time the burner is 
running, press and hold 
the reset button to disable 
the  burner.  The burner will 
remain off as long as the 
button is held.

Enables pump priming 
After the reset button has 
been held for 15 seconds. 
The button can then be 
clicked during the next 
ignition sequence to enter 
pump prime mode.

Run (igniter is shut off)

No action

No action

Pump Prime

No action

Exit Pump Prime mode and return to Standby

g

n

i

h

s

a

l

F

y

l

s

u

o

u

n

i

t

n

o

C

n

O

r

o

l

o

C

t

h

g

i

L

t

u

o

k

c

o

L

tf

o

S

t

u

o

k

c

o

L

)

d

r

a

H

(

d

e

t

c

ir

t

s

e

R

d

e

R

Green

Flame Sensed during normal operation (Could be stray
light during standby)

Recycle

Yellow

Control is in pump prime mode 

or

N/A

Table 10

Reset Button Operation

Table 11

Status Light Function

Reset button currently held for 15+ seconds.

Heating Sequence − Actions & Responses

1.

Action: Thermostat calls for heat

 (W terminal is en-

ergized)

Response:

D

ST9103A control (A15) closes oil primary control
TR−TW contacts.

D

After 15−second prepurge, power is sent to the oil
delay valve, ignition occurs and flame is
established.

D

Igition sequence continues for 10 seconds after
flame is sensed. Oil will continue to flow as long as
cad cell senses flame.

D

Heat fan on ramp timing begins. When timing is
complete, the indoor blower is at heat speed and
warm air is delivered to the controlled space.

2.

Action: Thermostat ends call for heat

 (W terminal

is de−energized)

Response:

D

After the thermostat is satisfied, the thermostat
circuit opens. The oil delay valve and burner are
de−energized.

D

Burner is de−energized.

D

Heat fan off ramp timing begins. When timing is
complete, indoor blower is de−energized.

D

Blower control returns to standby mode (oil prima-
ry control and indoor blower are off).

3.

Action: Burner fails to light

Response:

D

Oil primary control enters soft lockout after ignition
failure (15 seconds without flame being sensed).
Push reset button on primary control for one sec-
ond to reset soft lockout.

D

After soft lockout reset, oil primary control allows
second ignition attempt. Primary control enters
hard lockout after second ignition failure (15 sec-
onds without flame being sensed). Push reset but-
ton on primary control for 15 seconds until light on
control turns yellow to reset hard lockout.

D

Burner motor is de−energized.

4.

Action: Established flame fails

Response:

D

Burner motor is de−energized and oil primary con-
trol goes into recycle mode.

D

If the fan off delay is longer than the recycle timing,
the indoor blower continues to run on heating
speed through the next trial for ignition.

5.

Action: Limit Switch Opens

Response:

D

Oil primary control de−energizes burner.

D

Indoor blower is energized immediately at cool
speed.

D

A15 control opens oil primary control TR−TW con-
tacts.

D

Indoor blower runs as long as limit stays open.

6.

Action: Limit Switch Closes

Response: If there is a heating demand, A15 control
energizes oil primary control and ignition sequence
begins.

Troubleshooting

Burner failure or improper operation can result from a num-
ber of different causes. Often the cause can be pinpointed
by observing the different types of failure or by the process
of elimination. The following troubleshooting charts list
some failures, causes and a sequence of steps to isolate
the point of failure. Check the simplest and most obvious
items before progressing to other items.

Содержание SLO183UFV Series

Страница 1: ...3UFV Unit Dimensions 2 SLO183UFV Unit Parts Arrangement 3 SLO183UFV Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Locate Level the Unit 6 Adjustments 7 Venting 7 Flue Conn...

Страница 2: ...ELECTRICAL INLET Right Side Only OIL PIPING INLET Left Side Only OPT OUTDOOR COMBUSTION AIR INLET CENTERING HOLE Field Fabricate Right Side only RETURN AIR OPENING Either Side 3 4 19 A B C D AIR FLOW...

Страница 3: ...MIT SWITCH INDOOR BLOWER CAPACITOR BLOWER CONTROL Figure 2 SLO183UFV AFG Burner Parts Arrangement ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WI...

Страница 4: ...the furnace burner IMPORTANT An opening to the outside for combustion air is strongly recommended especially in new homes Refer to table 1 or the unit rating plate for specific combustion air opening...

Страница 5: ...ed at the same time as the furnace much more air is required to ensure proper combustion and to prevent a down draft situation Insufficient amounts of air also cause incomplete combustion which can re...

Страница 6: ...same cross sec tional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall be no less than 3 76 mm In calculating free area the blocking ef...

Страница 7: ...spect the spark transformer leads also to ensure they are still attached to the electrodes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flang...

Страница 8: ...nts and should be consulted before installation of unit 2 The vent connector should be as short as possible to do the job 3 The vent connector should not be smaller than the outlet diameter of the ven...

Страница 9: ...operation remain con nected to the common venting system If venting system has been installed improperly the system must be cor rected as outlined in the previous section 1 Seal any unused openings i...

Страница 10: ...adiation shields should extend from the top of the unit to the top of the flue pipe NON COMBUSTIBLE SPACERS RADIATION SHIELDS SEE NOTE 1 7 178 mm min 12 305 mm min A A B SEE NOTE 3 SEE NOTE 2 Supply R...

Страница 11: ...2 12 mm OD Tubing 0 0 0 84 25 6 93 28 3 100 30 5 100 30 5 2 0 6 73 22 3 85 25 9 100 30 5 100 30 5 4 1 2 63 19 2 77 23 5 100 30 5 100 30 5 6 1 8 52 15 8 69 21 0 100 30 5 100 30 5 8 2 4 42 12 8 60 18 3...

Страница 12: ...ctory and field for oil leaks Oil Pipe Heater Optional A heater for the oil pipe is available for applications that are located in cold climates The heater warms the oil pipe to assist the initial sta...

Страница 13: ...Page 13 Figure 7 Typical SLO183UFV Wiring Diagram OIL DELAY A15 A54 9 1 ST9103A...

Страница 14: ...ams 1 Heat 1 Cool ComfortSense 7000 L7724U 1 Heat 2 Cool ComfortSense 7000 L7724U 1 Heat 1 Cool ComfortSense 7000 L7724U with Thermostat Dehumidification Mode 1 Heat 2 Cool ComfortSense 7000 L7724U wi...

Страница 15: ...ge Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L77...

Страница 16: ...of each cooling demand to allow for greater humidity removal and to conserve energy If after 7 1 2 minutes the Y demand is not met 100 CFM is supplied until the demand is satisfied OFF CALL 100 82 Y...

Страница 17: ...wer speed For example if the unit is operating at 1000 CFM the CFM LED will flash 10 times At times the light may appear to flicker or glow This takes place when the control is communicating with the...

Страница 18: ...5 NORM N A N A N A N A 1300 615 1200 565 1400 660 1200 565 1000 470 800 380 N A N A N A N A Same as NORM 1190 560 1020 480 850 400 680 320 Model SLO183UFV135 150 Units Do not use 150 Do not use 135 N...

Страница 19: ...rom picking up radiant heat Set thermostat to its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in temp...

Страница 20: ...oosen the air band screw and rotate the band This is the starting point Do not stop here 4 CO2 Test Again take this sample at the vent pipe With the unit firing at a trace of smoke take a sample of th...

Страница 21: ...ps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush sweep down the outer drum of the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove t...

Страница 22: ...nal is de energized Response D After the thermostat is satisfied the thermostat circuit opens The oil delay valve and burner are de energized D Burner is de energized D Heat fan off ramp timing begins...

Страница 23: ...peed ramps down Circulat ing fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory con...

Страница 24: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Страница 25: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Страница 26: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Страница 27: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Страница 28: ...d heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High stac...

Отзывы: