Page 10
have flue pipe as short and direct as possible. Where two
or more appliances vent into a common flue, the area of
the common flue should be at least equal to the area of the
largest flue or vent connector, plus 50% of the area of any
additional flues or vent connectors. Install a barometric
draft control (provided) and flue pipe according to instruc-
tions packed with control.
Inspect flue pipe annually. Clean soot or ash from flue pipe,
if necessary. If pipe is rusted, replace.
Barometric Draft Control Installation
Install the provided barometric draft control in the flue pipe
at least 12 inches
beyond the furnace flue outlet to pro-
vide space for flue gas sampling. The barometric draft con-
trol may be installed in either vertical or horizontal sections
of the flue pipe; however, it should be positioned
no more
than 18"
beyond the furnace flue outlet. Follow the instruc-
tions packed with the barometric draft control.
Alternate Side Flue Connections
The vent pipe may exit the top or sides of the cabinet. A
hole is provided in the top cap for top exit. For side exit, lo-
cate the center hole punched in the side of the cabinet. See
unit dimensions on page 2. Using it as the center point,
cut a 6 inch (152 mm) round hole in the cabinet’s side.
Install the barometric draft control within 18 inches of
the furnace flue outlet.
Attach the provided finishing
plate to cover rough edges.
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
ÏÏÏÏÏÏÏÏ
1" (25 mm) min
Figure 6
COMBUSTIBLE
MATERIAL
Radiation Shield Installation
SLO183UFV UNIT
(TOP)
SLO183UFV UNIT
(FRONT)
RADIATION
SHIELDS
FLUE
PIPE
UNIT
CABINET
NOTE 1−Radiation shields must be constructed of 24 gauge sheet
metal
minimum
.
NOTE 2−Radiation shields required when A is less than 9" (229 mm).
NOTE 3−Radiation shields should extend from the top of the unit to
the top of the flue pipe.
NON−
COMBUSTIBLE
SPACERS
RADIATION SHIELDS
(SEE NOTE 1)
7" (178
mm) min
12" (305 mm) min
A
A
B
SEE
NOTE
3
SEE
NOTE 2
Supply & Return Air Plenums
Secure return air plenum to unit using sheet metal screws.
NOTE − The following are suggested procedures that should
be followed when installing the supply air plenum.
1. Use sealing strips of fiberglass.
2. In all cases, the plenum should be secured to furnace or
evaporator cabinet with sheet metal screws.
3. Install supply and return air ducts as desired.
Oil Supply Line Sizing
Ensure that the restrictions of the piping system, plus any
lift involved, do not exceed the capability of the oil pump.
Use the following guidelines when determining whether to
use a single−or two−stage oil pump.
One−Pipe System
When using a one−pipe system (see figure 7), even with
the oil tank that is above the burner and a vacuum of 6"
(152 mm) Hg or less, a single−stage fuel pump with a sup-
ply line and no return line should be adequate.
Manual bleeding of the fuel pump is required on initial start
up. Failure to bleed air from the oil pump could result in an
air lock/oil starvation condition.
NOTE − As an extra precaution, cycle heating on and off
ten times after bleeding air from the oil pump. This will elim-
inate air in the gun assembly.
Figure 7
Oil Piping − One-Pipe System
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓÓÓ
AIR VENT
FILL PIPE
OIL
TANK
FUEL PUMP
AUX
FILTER
SHUT−OFF
VALVE
8 ft (2.4 m)
Maximum
One Pipe Lift
To determine the correct tubing size for piping, refer to table 3
.
Table 3
One−Pipe Oil Line Sizing
Line Length
Pipe Diameter (OD Tubing)
0−50’ (15 m)
3/8" (10 mm)
51−100’ (15 m)
1/2" (12 mm)
Two−Pipe System
When using a two−pipe system (see figure 8) with the oil
tank below the level of the burner, use a single−stage fuel
pump in lift conditions of up to 10 feet (3 m) and/or a vacu-
um of 10" (254 mm) Hg or less. Use a two−stage fuel pump