background image

Page 17

Figure 10

A54

A15

Heat Pump Applications

Clip red jumper from R to O
close to R terminal.

Make pigtail 
connection and run wire from
terminal O to O terminal on
thermostat.

To blower

motor

ADJUST

The 

ADJUST

 pins affect blower motor speed during cool-

ing operation only. The ADJUST feature allows the motor
to run at normal speed, approximately 15% higher than
normal speed, or 15% lower than normal speed during the
cooling mode. Table 7 gives three rowsNORM, (+), and
(–) with their respective CFM volumes. Notice that the nor-
mal NORM" adjustment setting for cool speed position C
in table 7 is 800 CFM. The (+)" adjustment setting for that
position is 920 CFM (115% of 800 CFM) and the (–)" ad-
justment setting is 680 CFM (85% of 800 CFM). After the
adjustment setting has been determined, choose the re-
maining speed settings from those offered in the table in
that row.

HEAT

The unit is factory−set to run at the middle of heating rise
range as shown on the unit rating plate. The jumper on the
tap marked 

HEAT

 must remain in the position given in table

7.

The 

HEAT

 jumper is used to determine CFM during heat-

ing operation only. These jumper selections are activated
only when W1 is energized.

During the heat ON delay, the blower runs at 13% CFM for
the first minute, 50% CFM for the second minute, and full
CFM after two minutes.

OFF

CALL

100%

82%

50%

13%

W

60
sec

60
sec

210 seconds

w

W − Heat Demand Present

w − Heat Demand Satisfied

When the demand for heat is met, the blower ramps down
to 82% CFM for 3−1/2 minutes, then turns off.

TEST

The TEST pin is available to bypass the blower control and
run the motor at approximately 70% to make sure that the
motor is operational. This is used mainly in troubleshoot-
ing. The G terminal must be energized for the motor to run.

CFM LED

The

 CFM

 LED located on the blower control flashes one

time per 100 cfm to indicate selected blower speed.  For
example, if the unit is operating at 1000 CFM, the 

CFM

LED will flash 10 times.

At times, the light may appear to flicker or glow. This takes
place when the control is communicating with the motor
between cycles. This is normal operation.

After the CFM for each application has been determined,
the jumper settings must be adjusted to reflect those given
in table 7. From the table, determine which row most close-
ly matches the desired CFM. Once a specific row has been
chosen (+, NORMal, or −), CFM volumes from other rows
cannot be used. Below are descriptions of the jumper
selections.

The variable speed motor slowly ramps up to and down
from the selected air flow during both cooling and heating
demand. This minimizes noise and eliminates the initial
blast of air when the blower is initially energized.

Continuous Fan

When the thermostat is set for Continuous Fan" operation
and there is no demand for heating or cooling, the blower
control will provide 50% of the 

COOL

 CFM selected.

OFF

CALL

50%

G

g

G − Fan switch ON

g − Fan switch OFF

NOTE − With the proper thermostat and subbase, continu-
ous blower operation is possible by closing the R to G cir-
cuit.

Dehumidification

The A54 blower control (see figure 11) includes a HUM ter-
minal which provides for connection of a humidistat. The
JW1 jumper on the blower control must be cut to activate
the HUM terminal. The humidistat must be wired to open
on humidity rise. When the dehumidification circuit is used,
the variable speed motor will reduce the selected air flow
rate by 18% when humidity levels are high. An LED (D1)
lights when the blower is operating in the dehumidification
mode.

Humidification

Terminals are provided on the A15 control for 120 volt out-
put to operate a humidifier. The HUM" terminal is ener-
gized when there is a call for heat. See figure 13.

Indoor Air Quality (IAQ) Accessory

An EAC terminal is provided on the A15 control for 120 volt
output to an indoor air quality accessory. The EAC terminal
is energized when there is a call for heat, cool, or continu-
ous blower. See figure 13.

Содержание SLO183UFV Series

Страница 1: ...3UFV Unit Dimensions 2 SLO183UFV Unit Parts Arrangement 3 SLO183UFV Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Locate Level the Unit 6 Adjustments 7 Venting 7 Flue Conn...

Страница 2: ...ELECTRICAL INLET Right Side Only OIL PIPING INLET Left Side Only OPT OUTDOOR COMBUSTION AIR INLET CENTERING HOLE Field Fabricate Right Side only RETURN AIR OPENING Either Side 3 4 19 A B C D AIR FLOW...

Страница 3: ...MIT SWITCH INDOOR BLOWER CAPACITOR BLOWER CONTROL Figure 2 SLO183UFV AFG Burner Parts Arrangement ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WI...

Страница 4: ...the furnace burner IMPORTANT An opening to the outside for combustion air is strongly recommended especially in new homes Refer to table 1 or the unit rating plate for specific combustion air opening...

Страница 5: ...ed at the same time as the furnace much more air is required to ensure proper combustion and to prevent a down draft situation Insufficient amounts of air also cause incomplete combustion which can re...

Страница 6: ...same cross sec tional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall be no less than 3 76 mm In calculating free area the blocking ef...

Страница 7: ...spect the spark transformer leads also to ensure they are still attached to the electrodes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flang...

Страница 8: ...nts and should be consulted before installation of unit 2 The vent connector should be as short as possible to do the job 3 The vent connector should not be smaller than the outlet diameter of the ven...

Страница 9: ...operation remain con nected to the common venting system If venting system has been installed improperly the system must be cor rected as outlined in the previous section 1 Seal any unused openings i...

Страница 10: ...adiation shields should extend from the top of the unit to the top of the flue pipe NON COMBUSTIBLE SPACERS RADIATION SHIELDS SEE NOTE 1 7 178 mm min 12 305 mm min A A B SEE NOTE 3 SEE NOTE 2 Supply R...

Страница 11: ...2 12 mm OD Tubing 0 0 0 84 25 6 93 28 3 100 30 5 100 30 5 2 0 6 73 22 3 85 25 9 100 30 5 100 30 5 4 1 2 63 19 2 77 23 5 100 30 5 100 30 5 6 1 8 52 15 8 69 21 0 100 30 5 100 30 5 8 2 4 42 12 8 60 18 3...

Страница 12: ...ctory and field for oil leaks Oil Pipe Heater Optional A heater for the oil pipe is available for applications that are located in cold climates The heater warms the oil pipe to assist the initial sta...

Страница 13: ...Page 13 Figure 7 Typical SLO183UFV Wiring Diagram OIL DELAY A15 A54 9 1 ST9103A...

Страница 14: ...ams 1 Heat 1 Cool ComfortSense 7000 L7724U 1 Heat 2 Cool ComfortSense 7000 L7724U 1 Heat 1 Cool ComfortSense 7000 L7724U with Thermostat Dehumidification Mode 1 Heat 2 Cool ComfortSense 7000 L7724U wi...

Страница 15: ...ge Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L77...

Страница 16: ...of each cooling demand to allow for greater humidity removal and to conserve energy If after 7 1 2 minutes the Y demand is not met 100 CFM is supplied until the demand is satisfied OFF CALL 100 82 Y...

Страница 17: ...wer speed For example if the unit is operating at 1000 CFM the CFM LED will flash 10 times At times the light may appear to flicker or glow This takes place when the control is communicating with the...

Страница 18: ...5 NORM N A N A N A N A 1300 615 1200 565 1400 660 1200 565 1000 470 800 380 N A N A N A N A Same as NORM 1190 560 1020 480 850 400 680 320 Model SLO183UFV135 150 Units Do not use 150 Do not use 135 N...

Страница 19: ...rom picking up radiant heat Set thermostat to its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in temp...

Страница 20: ...oosen the air band screw and rotate the band This is the starting point Do not stop here 4 CO2 Test Again take this sample at the vent pipe With the unit firing at a trace of smoke take a sample of th...

Страница 21: ...ps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush sweep down the outer drum of the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove t...

Страница 22: ...nal is de energized Response D After the thermostat is satisfied the thermostat circuit opens The oil delay valve and burner are de energized D Burner is de energized D Heat fan off ramp timing begins...

Страница 23: ...peed ramps down Circulat ing fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory con...

Страница 24: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Страница 25: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Страница 26: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Страница 27: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Страница 28: ...d heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High stac...

Отзывы: