Troubleshooting:  Burner starts, but no flame is established.

Source

Procedure

Causes

Correction

Oil Supply

Check tank gauge or use dip
stick.

No oil in tank

Fill tank.

Coat dip stick with litmus paste
and insert into bottom of tank.

Water in oil tank

If water depth exceeds 1 inch,
pump or drain water.

Listen for pump whine.

Tank shut−off valve closed

Open valve.

Oil Filters & Oil Line

Listen for pump whine.

Oil line filter is plugged

Replace filter cartridges.

Kinks or restriction in oil line

Repair or replace oil line.

Plugged fuel pump strainer

Clean strainer or replace pump.

Open bleed valve or gauge port.
Start the burner. No oil or milky
oil indicates loss or prime.

Air leak in oil supply line

Locate and correct leak.

Tighten all connections.

Oil Pump

Install pressure gauge on pump
and read pressure. Should not
be less than 140 psi.

Pump is partially or completely
frozen. No pressure and the
motor locks out on overload.

Replace pump.

Coupling disengaged or broken
− no pressure

Re−engage or replace coupling.

Fuel pressure too low

Adjust to 140 psi.

Nozzle

Observe the oil spray (gun as-
sembly must be removed from
unit). Inspect the nozzle for
plugged orifice or carbon build−
up around orifice.

Nozzle orifice plugged

Replace nozzle with the same
size, spray angle, and spray
pattern.

Nozzle strainer plugged

Poor or off center spray

Ignition Electrodes

Remove gun assembly and in-
spect electrodes.

Fouled or shorted electrodes

Clean or replace electrodes.

Dirty electrodes

Eroded electrode tips

Clean electrode tips and use
T−501 gauge to reset the gap to
5/32 inches and correctly posi-
tion tips.

Improper electrode gap spacing

Improper position of electrode
tips

Bad buss bar connection

Retension and realign.

Cracked or chipped insulators

Replace electrode.

Ignition

Transformer

Start burner and observe spark.
Check line voltage to transform-
er primary.

Low line voltage

Check voltage at power source.
Correct cause of voltage drop
or call the power company.

Burned out transformer wind-
ings.

Replace the transformer.

No spark or weak spark

Properly ground the transformer
case.

 Burner Motor

Motor does not come up to
speed and trips out on overload.
Turn off power and rotate blower
wheel by hand to check for bind-
ing or excessive drag.

Low line voltage

Check voltage at power source.
Correct cause of voltage drop
or the call power company.

Pump or blower overloading
motor

Correct cause of overloading.

Faulty motor

Replace motor.

Содержание SLO183UFV Series

Страница 1: ...3UFV Unit Dimensions 2 SLO183UFV Unit Parts Arrangement 3 SLO183UFV Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Locate Level the Unit 6 Adjustments 7 Venting 7 Flue Conn...

Страница 2: ...ELECTRICAL INLET Right Side Only OIL PIPING INLET Left Side Only OPT OUTDOOR COMBUSTION AIR INLET CENTERING HOLE Field Fabricate Right Side only RETURN AIR OPENING Either Side 3 4 19 A B C D AIR FLOW...

Страница 3: ...MIT SWITCH INDOOR BLOWER CAPACITOR BLOWER CONTROL Figure 2 SLO183UFV AFG Burner Parts Arrangement ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WI...

Страница 4: ...the furnace burner IMPORTANT An opening to the outside for combustion air is strongly recommended especially in new homes Refer to table 1 or the unit rating plate for specific combustion air opening...

Страница 5: ...ed at the same time as the furnace much more air is required to ensure proper combustion and to prevent a down draft situation Insufficient amounts of air also cause incomplete combustion which can re...

Страница 6: ...same cross sec tional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall be no less than 3 76 mm In calculating free area the blocking ef...

Страница 7: ...spect the spark transformer leads also to ensure they are still attached to the electrodes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flang...

Страница 8: ...nts and should be consulted before installation of unit 2 The vent connector should be as short as possible to do the job 3 The vent connector should not be smaller than the outlet diameter of the ven...

Страница 9: ...operation remain con nected to the common venting system If venting system has been installed improperly the system must be cor rected as outlined in the previous section 1 Seal any unused openings i...

Страница 10: ...adiation shields should extend from the top of the unit to the top of the flue pipe NON COMBUSTIBLE SPACERS RADIATION SHIELDS SEE NOTE 1 7 178 mm min 12 305 mm min A A B SEE NOTE 3 SEE NOTE 2 Supply R...

Страница 11: ...2 12 mm OD Tubing 0 0 0 84 25 6 93 28 3 100 30 5 100 30 5 2 0 6 73 22 3 85 25 9 100 30 5 100 30 5 4 1 2 63 19 2 77 23 5 100 30 5 100 30 5 6 1 8 52 15 8 69 21 0 100 30 5 100 30 5 8 2 4 42 12 8 60 18 3...

Страница 12: ...ctory and field for oil leaks Oil Pipe Heater Optional A heater for the oil pipe is available for applications that are located in cold climates The heater warms the oil pipe to assist the initial sta...

Страница 13: ...Page 13 Figure 7 Typical SLO183UFV Wiring Diagram OIL DELAY A15 A54 9 1 ST9103A...

Страница 14: ...ams 1 Heat 1 Cool ComfortSense 7000 L7724U 1 Heat 2 Cool ComfortSense 7000 L7724U 1 Heat 1 Cool ComfortSense 7000 L7724U with Thermostat Dehumidification Mode 1 Heat 2 Cool ComfortSense 7000 L7724U wi...

Страница 15: ...ge Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L77...

Страница 16: ...of each cooling demand to allow for greater humidity removal and to conserve energy If after 7 1 2 minutes the Y demand is not met 100 CFM is supplied until the demand is satisfied OFF CALL 100 82 Y...

Страница 17: ...wer speed For example if the unit is operating at 1000 CFM the CFM LED will flash 10 times At times the light may appear to flicker or glow This takes place when the control is communicating with the...

Страница 18: ...5 NORM N A N A N A N A 1300 615 1200 565 1400 660 1200 565 1000 470 800 380 N A N A N A N A Same as NORM 1190 560 1020 480 850 400 680 320 Model SLO183UFV135 150 Units Do not use 150 Do not use 135 N...

Страница 19: ...rom picking up radiant heat Set thermostat to its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in temp...

Страница 20: ...oosen the air band screw and rotate the band This is the starting point Do not stop here 4 CO2 Test Again take this sample at the vent pipe With the unit firing at a trace of smoke take a sample of th...

Страница 21: ...ps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush sweep down the outer drum of the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove t...

Страница 22: ...nal is de energized Response D After the thermostat is satisfied the thermostat circuit opens The oil delay valve and burner are de energized D Burner is de energized D Heat fan off ramp timing begins...

Страница 23: ...peed ramps down Circulat ing fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory con...

Страница 24: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Страница 25: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Страница 26: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Страница 27: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Страница 28: ...d heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High stac...

Отзывы: