Level the unit from side to side and from front to rear. If the
furnace is not level, place fireproof wedges or shims be-
tween the low side of the furnace and the floor. Make sure
the weight of the furnace is distributed evenly on all four
corners. Strain on sides of cabinet causing cracking and
popping noises may occur if weight of furnace is not evenly
distributed.

Adjustments

Neither the nozzle setting nor the air adjustments are fac-
tory set. The furnace is fire−tested and the limit control is
checked to make sure it functions properly; no factory set-
tings are made. During installation, the furnace must be
set up." The installing dealer/contractor must have and
use proper test equipment in order to correctly set up the
oil furnace. Proper testing equipment is required to ensure
correct operation of the unit. The use of test equipment is
now more critical than ever due to tighter tolerances need-
ed to keep the furnace operating efficiently.

Among the test equipment for an oil furnace, the proper
combustion test kit should contain the following:

S

Draft gauge

S

CO

2

 or O

2

 analyzer

S

Smoke tester

S

Pressure gauge

S

High temperature thermometer

S

Beckett T−501 or Z−2000 nozzle gauge

S

Oil vacuum gauge

S

Knowledge of proper test equipment operation

CAUTION

Improper nozzle and/or air adjustment of this unit
may result in sooting problems. Refer to the follow-
ing section for correct adjustment procedures.

Adjusting the Nozzle

Proper adjustment of the nozzle assembly is critical. Before
the flue pipe and oil lines are installed, the nozzle assembly
must be checked for proper depth and alignment. You must
remove the entire burner assembly (not just the nozzle) from
the furnace to check the nozzle depth and alignment. The
smaller sized firing nozzle has been factory−installed. This
should be verified by the installer. A larger nozzle has been
provided in the bag assembly for use with SLO183UFV86,
114 and 150 units. Inspect the spark transformer leads also
to ensure they are still attached to the electrodes.

The burner assembly is attached to the vestibule panel by
three nuts. Slots are provided in the mounting flange for re-
moving the burner assembly from the vestibule. Loosen
the nuts and turn the whole burner assembly clockwise
(figure 4) to remove the entire burner assembly from the
furnace. There is adequate wire to remove the burner with-
out disconnecting wires. Once removed, turn the burner
around in the vest panel area. 

Figure 4

SLO183UFV Series Burner Removal

First, loosen three nuts which

attach burner to vest panel.

Next, rotate burner clockwise
on slots then pull toward you.

To correctly check and adjust the nozzle depth and align-
ment, use the Beckett T−501 or Z−2000 gauge.

To check the oil nozzle depth, insert the small end of the
gauge into the end of the cone and measure from the flat of
the end cone to the face of the nozzle. When nozzle depth
is correct, the tip of the nozzle should just touch the end of
the gauge. Refer to the illustration sheet provided with the
gauge. Note that the scale side of the gauge is not used for
this purpose. If necessary, loosen the escutcheon plate se-
curing screw and slide the entire nozzle assembly forward
or backward within the air tube (figure 5). Re−secure es-
cutcheon plate screw when adjustment is completed.

To check nozzle alignment, again insert the small end of
gauge into the end cone and measure the nozzle and
electrode alignment against the center lines marked on
the gauge (again refer to enclosed illustration sheet). If
the nozzle is not centered, but found to be too far left or
right, a new nozzle assembly will need to be ordered. Do
not attempt to adjust by bending the 90 degree elbow in
the oil line.

Take care to properly re−install burner assembly when
nozzle adjustment has been completed.

Figure 5

Beckett Oil Burner Nozzle Adjustment

Burner must be removed from

furnace for this procedure.

1

2

T−501 Gauge

Escutcheon Plate

To Adjust Nozzle

1−Loosen escutcheon plate screw.

2−Slide entire nozzle/electrode assembly back and forth inside air
tube until nozzle just touches gauge.

Содержание SLO183UFV Series

Страница 1: ...3UFV Unit Dimensions 2 SLO183UFV Unit Parts Arrangement 3 SLO183UFV Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Locate Level the Unit 6 Adjustments 7 Venting 7 Flue Conn...

Страница 2: ...ELECTRICAL INLET Right Side Only OIL PIPING INLET Left Side Only OPT OUTDOOR COMBUSTION AIR INLET CENTERING HOLE Field Fabricate Right Side only RETURN AIR OPENING Either Side 3 4 19 A B C D AIR FLOW...

Страница 3: ...MIT SWITCH INDOOR BLOWER CAPACITOR BLOWER CONTROL Figure 2 SLO183UFV AFG Burner Parts Arrangement ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WI...

Страница 4: ...the furnace burner IMPORTANT An opening to the outside for combustion air is strongly recommended especially in new homes Refer to table 1 or the unit rating plate for specific combustion air opening...

Страница 5: ...ed at the same time as the furnace much more air is required to ensure proper combustion and to prevent a down draft situation Insufficient amounts of air also cause incomplete combustion which can re...

Страница 6: ...same cross sec tional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall be no less than 3 76 mm In calculating free area the blocking ef...

Страница 7: ...spect the spark transformer leads also to ensure they are still attached to the electrodes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flang...

Страница 8: ...nts and should be consulted before installation of unit 2 The vent connector should be as short as possible to do the job 3 The vent connector should not be smaller than the outlet diameter of the ven...

Страница 9: ...operation remain con nected to the common venting system If venting system has been installed improperly the system must be cor rected as outlined in the previous section 1 Seal any unused openings i...

Страница 10: ...adiation shields should extend from the top of the unit to the top of the flue pipe NON COMBUSTIBLE SPACERS RADIATION SHIELDS SEE NOTE 1 7 178 mm min 12 305 mm min A A B SEE NOTE 3 SEE NOTE 2 Supply R...

Страница 11: ...2 12 mm OD Tubing 0 0 0 84 25 6 93 28 3 100 30 5 100 30 5 2 0 6 73 22 3 85 25 9 100 30 5 100 30 5 4 1 2 63 19 2 77 23 5 100 30 5 100 30 5 6 1 8 52 15 8 69 21 0 100 30 5 100 30 5 8 2 4 42 12 8 60 18 3...

Страница 12: ...ctory and field for oil leaks Oil Pipe Heater Optional A heater for the oil pipe is available for applications that are located in cold climates The heater warms the oil pipe to assist the initial sta...

Страница 13: ...Page 13 Figure 7 Typical SLO183UFV Wiring Diagram OIL DELAY A15 A54 9 1 ST9103A...

Страница 14: ...ams 1 Heat 1 Cool ComfortSense 7000 L7724U 1 Heat 2 Cool ComfortSense 7000 L7724U 1 Heat 1 Cool ComfortSense 7000 L7724U with Thermostat Dehumidification Mode 1 Heat 2 Cool ComfortSense 7000 L7724U wi...

Страница 15: ...ge Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L77...

Страница 16: ...of each cooling demand to allow for greater humidity removal and to conserve energy If after 7 1 2 minutes the Y demand is not met 100 CFM is supplied until the demand is satisfied OFF CALL 100 82 Y...

Страница 17: ...wer speed For example if the unit is operating at 1000 CFM the CFM LED will flash 10 times At times the light may appear to flicker or glow This takes place when the control is communicating with the...

Страница 18: ...5 NORM N A N A N A N A 1300 615 1200 565 1400 660 1200 565 1000 470 800 380 N A N A N A N A Same as NORM 1190 560 1020 480 850 400 680 320 Model SLO183UFV135 150 Units Do not use 150 Do not use 135 N...

Страница 19: ...rom picking up radiant heat Set thermostat to its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in temp...

Страница 20: ...oosen the air band screw and rotate the band This is the starting point Do not stop here 4 CO2 Test Again take this sample at the vent pipe With the unit firing at a trace of smoke take a sample of th...

Страница 21: ...ps from the clean out tubes Remove flue access elbow 3 Using a long spiral wire brush sweep down the outer drum of the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove t...

Страница 22: ...nal is de energized Response D After the thermostat is satisfied the thermostat circuit opens The oil delay valve and burner are de energized D Burner is de energized D Heat fan off ramp timing begins...

Страница 23: ...peed ramps down Circulat ing fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory con...

Страница 24: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Страница 25: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Страница 26: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Страница 27: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Страница 28: ...d heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High stac...

Отзывы: